Model XP2F
Installation, Operation, and Maintenance Manual
N-XP2F IOM V1.0-4.5
Page 22 of 35
The Retransmission page shown in
allows the signal received from the transmitter to be
retransmitted via a 4-20mA output channel on the X35 to a PLC/SCADA system.
Figure 4.25
4.4.4
Calibration
4.4.4.1
Inputs
Description:
Used when the milliamps/volts measured on an input channel on the X35 differ from the
value measured on a multimeter or PLC/SCADA system. Allows the discrepancy to be eliminated.
Figure 4.26
The 4-20mA
output
channel the
signal will be
retransmitted
from
The minimum
and maximum
scaling for the
4-20mA
signal.
Input channel to
calibrate
Type of signal sent
to channel (4-20mA
or 0-10V)
Pressing “Select”
then displays
subsequent fields.
Reports current
signal X35 is
measuring.
Enter correct signal
measured on
multimeter/SCADA,
then press “Set Lo”.
Repeat for “Set
High”.