Direct Flush configuration
The ICU can adjust/activate the following settings
on the Direct Flush: sensor range; flush time;
12hr hygiene flush and siphonic trap.
The product must always be put into ICU
configuration mode (see page 13) before any
setting can be configured.
Configuring sensor range
Point the ICU at the Direct Flush sensor and press
the 1
sensor range button (the sensor blinks
green).
Decrease or increase the sensor range by pressing
the
and
buttons respectively. The sensor blinks
red when the min or max value is reached.
Press the
button to check the sensor range
setting - the sensor displays the current setting by
flashing green, see table.
Save setting and exit ICU configuration mode by
pressing the
button.
Exit without saving by pressing the
button.
Configuring sensor range using
the autorange function
Point the ICU at the Direct Flush sensor and press
the 7 autorange button.
Immediately stand clear of the sensor. Sensor
blinks green for 5 seconds, then a steady green
when setting complete. The sensor measures the
background reflections and sets the sensor range
to an appropriate setting.
Save setting and exit ICU configuration mode by
pressing the
button.
Exit without saving by pressing the
button.
Configuring flush time
Point the ICU at the Direct Flush sensor and press
the flush time button 2 (the sensor blinks green).
Decrease or increase the flush time by pressing the
and
buttons respectively. The sensor blinks
red when the min or max value is reached.
Press the
button to check the flush time setting
- the sensor displays the current setting
by flashing green, see table.
Save setting and exit ICU configuration mode by
pressing the
button.
Exit without saving by pressing the
button.
Activating the 12hr hygiene
flush cycle
Point the ICU at the Direct Flush sensor and press
the 5
hygiene cycle button (the sensor blinks
green).
Pressing the
and
buttons switches the hygiene
flush function on or off respectively. Press the
button to check the setting - the sensor flashes
green once if function is off or twice if it is on.
Save setting and exit ICU configuration mode by
pressing the
button.
Exit without saving by pressing the
button.
Activating the siphonic trap
refill function
Point the ICU at the Direct Flush sensor and press
the 8
siphonic trap button (the sensor blinks
green).
Pressing the
and
buttons switches the siphonic
trap refill function on or off respectively. Press the
button to check the setting - the sensor flashes
green once if function is off or twice if it is on.
Save setting and exit ICU configuration mode by
pressing the
button.
Exit without saving by pressing the
button.
Reset to factory settings
Point the ICU at the Direct Flush sensor and press
the 9
reset button (the sensor blinks green).
This sets all settings to the default factory settings.
Save all settings and exit ICU configuration mode
by pressing the
button.
Exit without saving by pressing the
button.
Number of flashes
1
2
3
4
5
Range (cm approx)
45
50
53
56
58
Number of flashes
1
2
3
4
5
Flush time (seconds)
3
5
7
9
11