NTP-G524 Install the Power Modules in the ONS 15454 M6 Shelf
This procedure installs the power modules in the ONS 15454 M6 system.
Purpose
#2 Phillips screwdriver
Tools/Equipment
•
NTP-G252 Install the ONS 15454 M6 Shelf , on page 24
•
NTP-G259 Open and Remove the Standard Door of the ONS 15454 M6
Shelf , on page 57
.
• Connect the chassis to the office ground. For detailed instructions on how
to ground the chassis, see the
Electrostatic Discharge and Grounding Guide
for Cisco CPT and Cisco ONS Platforms
.
Prerequisite Procedures
Required
Required/As Needed
Onsite
Onsite/Remote
None
Security Level
The plug-socket combination must be accessible at all times because it serves as the main disconnecting
device.
Statement 1019
Warning
Procedure
Step 1
Complete the necessary task as applicable:
•
DLP-G569 Install the AC Power Module in the ONS 15454 M6 Shelf, on page 85
•
DLP-G757 Replacing 15454-M6-AC With 15454-M6-AC2 Power module, on page 88
•
DLP-G758 Replacing 15454-M6-AC2 With 15454-M6-AC Power module, on page 89
•
DLP-G570 Install the DC Power Module in the ONS 15454 M6 Shelf, on page 90
•
DLP-G737 Replacing 15454-M6-DC With 15454-M6-DC20 Power Module, on page 93
•
DLP-G738 Replacing 15454-M6-DC20 With 15454-M6-DC Power Module, on page 95
Step 2
Complete the
NTP-G256 Install Power and Ground to the ONS 15454 M6 Shelf , on page 100
Stop. You have completed this procedure.
DLP-G569 Install the AC Power Module in the ONS 15454 M6 Shelf
This task installs the 15454-M6-AC or 15454-M6-AC2 power module in the ONS
15454 M6 system.
Purpose
Installing the ONS 15454 M6 Shelf
85
Installing the ONS 15454 M6 Shelf
NTP-G524 Install the Power Modules in the ONS 15454 M6 Shelf