Bulk Chassis Flow, CFM
Deflector Configuration
Case
295.6
215.3
No deflectors
Side to Side
135.8
97.7
Inlet and Outlet
ETSI Front to Rear
258.6
187.7
Only Inlet
ETSI Front to Side
166.9
120.5
Inlet and Outlet
ANSI Front to Rear
268.6
193.5
Only Inlet
ANSI Front to Side
NTP-G252 Install the ONS 15454 M6 Shelf
This procedure installs the shelf.
Purpose
• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
• ETSI only:
• Six M6 x 20 pan-head Phillips mounting screws
• ANSI only:
• Six #12-24 x 3/4 pan-head Phillips mounting screws
Tools/Equipment
NTP-G305 Unpack and Inspect the ONS 15454, ONS 15454 M2, and ONS 15454
M6 Shelves
Prerequisite Procedures
Required
Required/As Needed
Onsite
Onsite/Remote
None
Security Level
Stability hazard. The rack stabilizing mechanism must be in place, or the rack must be bolted to the
floor before you slide the unit out for servicing. Failure to stabilize the rack can cause the rack to tip
over.
Statement 1048
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations.
Statement 1045
Warning
Installing the ONS 15454 M6 Shelf
24
Installing the ONS 15454 M6 Shelf
NTP-G252 Install the ONS 15454 M6 Shelf