.- TECHNICAL FEATURES
8�1�- RGU-100B
AC Power supply
Rated voltage
230 V ~ ± 15%
Frequency
50 ... 60 Hz
Consumption
7.5 VA
Installation category
CAT III 300V
Monitoring features
Rated frequency of the monitored circuit
DC: 0 Hz - AC: 50 Hz - 1 kHz
Rated residual non-operating current
0.5 Idn
Rated conditional short-circuit current (Icc)
Depends on the circuit breaker
Rated short-time withstand current (Icw)
Uimp of the voltage source
4 kV (CAT III)
Relay outputs
Quantity
1
Maximum voltage open contacts
230 V ~
Maximum current
6 A
Maximum switching power
1500 VA
Electrical life (250V ~ / 5A)
60x10
3
Cycles
Mechanical life
10x10
6
Cycles
Digital output
Type
Optoisolated
Maximum voltage
230 V ~
Maximum current
0.1 A
Digital input
Type
Potential free contact
Insulation
5.3 kV
Input impedance
2 KΩ
RS-485 Communications
Communications protocol
Modbus RTU
Baud rate
4800 -9600 - 19200 - 38400 - 57600 - 115200 bps
Data bits
8
Stop bits
1 - 2
Parity
without, even, odd
User interface
Display
LCD custom (negative)
Keyboard
3 keys
LED
2 LED
Environmental features
Operating temperature
-10ºC ... +50 ºC
Storage temperature
-20 ºC ... +70 ºC
Relative humidity (without condensation)
5... 95%
Maximum altitude
2000 m
Summary of Contents for RGU-100B
Page 1: ...INSTRUCTION MANUAL Protection and monitoring relay RGU 100B M256B01 03 20A...
Page 2: ...2 RGU 100B Instruction Manual...
Page 47: ...47 Instruction Manual RGU 100B 11 CE CERTIFICATE...
Page 48: ...48 RGU 100B Instruction Manual...
Page 49: ...49 Instruction Manual RGU 100B...
Page 53: ...53 Instruction Manual RGU 100B...