H
Contactors
This board closes when Charging Station is powered ON for a power modules detection
procedure. This procedure may last around 5 minutes. If relays board remains closed for
a longer period of time, it means that one or more power modules haven't been detect-
ed. Check if they are correctly supplied.
Relays board has to be open in standby.
It will close too when Charging Station is charging in the DC side.
AC contactor closes when Charing Station is charging in the AC side.
DC Relays board:
AC Contactor:
DC Relays board
AC Contactor Raption 50
AC Contactor Raption 50 HV
AC Contactor Raption 50 EVO
AC Contactor Raption 100