Raption 150C
Instruction Manual
103
Value
Description
Local authorisation
off-line
ENABLED:
during offline period locally-authorized identifiers are
allowed to start charging
DISABLED:
during offline period locally-authorized identifiers are
NOT allowed to start charging
Stop transaction on
invalid ID
ENABLED:
stop existing Charge Transaction after response from
Central System when user is blocked, expired or invalid.
DISABLED
: Charge Transaction does not stop even if backend rejects
the user.
Metervalue (select
one or more)
List of supported values used in the MeterValue.
Transaction
message retry
interval
Number of seconds between transaction message attempts.
Note:
setting this value to 0 disables the attempts.
Transaction
message attempts
How many times the Charge Point should try to send a request to
the Central System.
Heartbeat interval
Number of seconds between Heartbeats.
Note:
setting this value to 0 disables the Heartbeat.
Metervalues sample
interval
Number of seconds between MeterValue during an ongoing Charge
Transaction.
Note:
setting this value to 0 disables the MeterValue.
WebSocket ping
interval
Number of seconds between Pings.
Note:
setting this value to 0 disables the Websocket Ping/Pong
Summary of Contents for RAPTION 150C CCS CHA
Page 1: ...Raption 150C Series INSTRUCTION MANUAL M358B01 03 22A...
Page 2: ...Raption 150C Instruction Manual 2...
Page 32: ...Raption 150C Instruction Manual 32 3 CONNECTOR DISABLED 4 CONNECTOR IN USE...
Page 35: ...Raption 150C Instruction Manual 35...
Page 59: ...Raption 150C Instruction Manual 59...
Page 93: ...Raption 150C Instruction Manual 93...
Page 107: ...Raption 150C Instruction Manual 107 Monitoring...
Page 115: ...Raption 150C Instruction Manual 115...