GETEST
Page 23 of 24
It won't switch on. Check the
safety switch
position
Error: the required current
cannot be reached. Do you
wish to continue
extrapolating data?
The MPC unit can not reach the
required current due to an unknown
cause. If allowed, the PDA will
extrapolate the values at the desired
current using the highest current
that it can
Connect the MPC to a mains socket
connected to an installation with less
impedance or to a generator with more
power. You may also try to reduce the load
Danger: Main contactor
failure. It won't switch off
There is a risk of electric shock.
The main contactor has broken and
the safety protection is no longer
valid
Contact the vendor.
Erratic voltages higher than
50V. Continue?
There is a risk of electric shock.
The erratic voltages are too high. It
is possible that one phase of the
network is earthed
Contact the manager of the installation
being tested.
Danger: very high loop
resistance, possible
connection error. Check
connections and make sure
no one is touching the
injection circuit. Do you wish
to continue?
There is a risk of electric shock.
Resistance found is too high, maybe
due to bad connections
Check connections and make sure no one is
touching the connectors/electrodes/auxiliary
earth,
remove
rust
from
connectors/electrodes/auxiliary earth
Warning: the unit may not
have enough power to inject
the required current. The loop
resistance is too high for the
indicated current. Do you
wish to continue?
There is a risk of electric shock.
The loop resistance is too high for
the requested current
MPC will apply the maximum power, but
will not be able to reach the required value
Error: impossible to reach the
required current; there is a
drop in the device's power
supply
voltage.
The
installation to which it is
connected is unable to supply
the
required
current.
A
minimum of 20 KVA is
needed. Do you wish to
continue extrapolating data?
You are requesting the MPC to
supply more power than the
electrical network is able to supply.
Power is equal to the earth
resistance times the square of the
current to be injected. If allowed,
the PDA will extrapolate the values
using a lower current than desired
Connect the MPC to a mains socket
connected to an installation with less
impedance or to a generator with more
power
Warning: a short-circuit has
been found in the output. The
current has been limited to 35
A. Check the connections.
Measured resistance less than 0 W
Check the connections.
There may be a metallic plane in the earth
Warning, resistance found is
greater than 120 ohms. Check
the connections. Do you wish
to continue?
There is a risk of electric shock.
Resistance found is too high
Check the connections and make sure no
one is touching the
connectors/electrodes/auxiliary earth,
remove rust from
connectors/electrodes/auxiliary earth
10.- MAINTENANCE AND TECHNICAL SERVICE
In the case of any query in relation to unit operation or malfunction, please contact the
CIRCUTOR, SA Technical Support Service.