background image

4�8�3�8- Unit information parameters�

The Modbus address is in decimal format.

The read function is valid for these variables.

Table 14:Modbus memory map (Table 8)

UNIT INFORMATION

Address 1

(1)

Address 2

(2)

Name

Description

Unit

7000-7001

7500

Identifier

Unit identifier. 

The value 183: 

DHB-4xx

-

7002-7003

7501

Status

Record of the current status of the unit.

-

7004-7005

7502

Control

Control record for the analogue output

%

7006-7007

7503

Minimum

Minimum value of the value currently being dis-

played

-

7008-7009

7504

Maximum

Maximum value of the value currently being dis-

played

-

7010-7011

7505

Displayed value

Value currently being shown on the display

-

7012-7013

7506

current time

Current time

-

7014-7015

7507

Wire resistance

Cable resistance

Ω

7016-7017

7508

ADC

ADC

7018-7019

7509

Terminal 

temperature

Temperature of the terminals. The measurement is 

only taken during the temperature measurement via 

the thermocouple sensors or during the measure-

ment time.

ºC

7020-7021

7510

Measured value

Value measured without performing the non-linear 

equation regression.

-

7022-7023

7511

EMF

EMF measurement at the unit's terminals, when the 

temperature is measured via thermocouples.

μV

7024-7025

7512

Resistance

Resistance measurement of the line when the tem-

perature measurement is taken via RTD.

Ω

(1)

 Value in two consecutive 16-bit records.

(2)

 Value in one 32-bit record.

 

53

Instruction Manual

DHB-402 DHB-424

Summary of Contents for DHB-402

Page 1: ...INSTRUCTION MANUAL M045B01 03 21A Indicator for process signals temperature and resistance DHB 402 DHB 424...

Page 2: ...2 DHB 402 DHB 424 Instruction Manual...

Page 3: ...llowing should be taken into consideration Incorrect handling or installation of the unit may result in injury to personnel as well as damage to the unit In particular handling with voltages applied m...

Page 4: ...G PARAMETERS 11 4 2 DISPLAY 11 4 3 BUTTON FUNCTIONS 12 4 4 OPEN COLLECTOR OUTPUT OC DHB 424 model 13 4 5 REGRESSION OF NON LINEAR EQUATIONS 13 4 6 ALARMS 14 4 7 CONFIGURATION 15 4 7 1 INPUT PARAMETERS...

Page 5: ...01 03 15A Global revision 02 16 M045B01 03 16A Changes in the following sections 3 3 1 3 3 2 4 6 5 03 21 M045B01 03 21A Changes in the following sections 4 7 1 1 Note The images of the units are solel...

Page 6: ...panel unit that measures standard analogue signals sent by sensors temperature RTD and Thermocouple resistance and current time There are 2 versions of the unit depending on the number of alarms and...

Page 7: ...from the use of products or accessories that did not come with the unit or that were made by other manufacturers If an anomaly or malfunction is detected in the unit do not use the unit to take any m...

Page 8: ...minals 1 10V Voltage input 9 AL1 Alarm 1 relay output NO 2 GND Ground voltage and current input 10 AL1 Alarm 1 relay output Common 3 20mA Current input 11 AL2 Alarm 2 relay output NO 4 60mV Thermocoup...

Page 9: ...NO 28 OC Open collector output NPN 10 AL1 Alarm 1 relay output Common 29 30 Not used 11 AL2 Alarm 2 relay output NO 31 AL3 Alarm 3 relay output Common 12 AL2 Alarm 2 relay output Common 32 AL3 Alarm...

Page 10: ...2 and DHB 424 models 3 4 2 Connection for measuring temperature Thermocouple Resistance and RTD 2 wires Resistance and RTD 3 wires DHB 402 DHB 424 1 8 J K N E R S Type DHB 402 DHB 424 1 8 R 400 4000 R...

Page 11: ...65 C Temperature Type PT100 RTD 200 850 C 205 855 C Temperature Type PT500 RTD 200 850 C 205 855 C Temperature Type PT1000 RTD 200 850 C 205 855 C Resistance Range 400 0 400 0 410 Range 4000 0 4000 0...

Page 12: ...nd upper colour Example In a temperature measurement you can program the display to be green when the voltage is below 10 C orange when it is between 10 C and 50 C and red for voltages above 50 C See...

Page 13: ...inearised function Figure 8 Regression of non linear equations Once the number of points with which the function will be linearised has been selected the number of functions is one fewer than the numb...

Page 14: ...d when the average value exceeds the upper value PrH and does not deactivate until it is below the lower value PrL n off the alarm is deactivated when the average value exceeds the upper value PrH and...

Page 15: ...Measured value Alarm deactivated Alarm activated 0 PrL PrH Measured value Alarm output Alarm activated Alarm deactivated 1 0 PrL PrH Measured value Alarm output Alarm deactivated Alarm activated Alarm...

Page 16: ...larms 1 2 3 and 4 end Display screen Figure 10 Accessing the setup menus The DHB 4xx does not record programming changes until the configuration is complete If the unit is reset before finishing the c...

Page 17: ...assword is correct the unit will display the parameters screen Figure 13 To permanently unlock the unit see 4 7 9 2 PASSWORD Note By default the unit comes without a password 4 7 1 INPUT PARAMETERS Th...

Page 18: ...Type S thermocouple Voltage input 0 10 V Current input 0 20 mA Voltage input 0 60 mV Current time To move from one option to another press the button repeatedly When you see the option you want valida...

Page 19: ...tton You can now select the position of the decimal point which will be flashing To select the position of the decimal point press the button Validate by pressing the button The unit goes back to the...

Page 20: ...the screen shown in Figure 17 appears Press the button to go back to the main screen of the input parameters menu Figure 13 Figure 17 Exit menu screen 4 7 2 REGRESSION OF NON LINEAR EQUATIONS This me...

Page 21: ...value X1 measured value corresponding to the first point in the equation The screen flashes between the symbol and the configured value Figure 20 Figure 20 Measured values configuration screens To ed...

Page 22: ...nit will go back to the screen shown in Figure 21 To move to the next parameter on the menu press the button When the button is pressed the unit goes to the main screen of the regression of non linear...

Page 23: ...t to another press the button repeatedly When you see the option you want validate by pressing the button The unit goes back to the screen shown in Figure 24 To move to the next parameter on the menu...

Page 24: ...splay In other words this is the display colour when the measured value is between the lower colour limit see section 4 7 3 5 LOWER COLOUR LIMIT and the upper colour limit see section 4 7 3 6 UPPER CO...

Page 25: ...tions press the button The colour options are Green Orange Red To move from one option to another press the button repeatedly When you see the option you want validate by pressing the button The unit...

Page 26: ...IMIT This screen is used to configure the value of the upper colour limit The screen flashes between the symbol and the configured value Figure 29 Figure 29 Upper colour limit screens To edit the para...

Page 27: ...sition of the decimal point press the button Validate by pressing the button The unit goes back to the screen shown in Figure 30 To move to the next parameter on the menu press the button When the but...

Page 28: ...t value 99999 4 7 3 9 EXITING THE MENU At the end of the menu the screen shown in Figure 32 appears Press the button to go back to the main screen of the display menu Figure 23 Figure 32 End of menu s...

Page 29: ...enu Figure 33 Default value Type of input that has been connected to the unit InP 4 7 4 2 ALARM TYPE This screen is used to select the alarm functionality see section 4 6 ALARMS The screen flashes bet...

Page 30: ...value validate by pressing the button You can now select the position of the decimal point which will be flashing To select the position of the decimal point press the button Validate by pressing the...

Page 31: ...DELAY This screen is used to configure the connection and disconnection delay for the alarm The screen flashes between the symbol and the configured value Figure 38 Figure 38 Connection disconnection...

Page 32: ...39 To move to the next parameter on the menu press the button When the button is pressed the unit goes to the main screen of the alarms menu Figure 33 Default value Alarm LEDs not interlocked OFF 4 7...

Page 33: ...n flashes between the symbol and the configured value Figure 42 S R DHB 424 Figure 42 Analogue output configuration screen meter To edit the parameter press the button S R DHB 424 Type of input that h...

Page 34: ...hen the button is pressed the unit goes to the main screen of the outputs menu Figure 41 Default value Voltage 0 10 V 4 7 8 3 ANALOGUE OUTPUT ZERO VALUE DHB 424 model This screen is used to configure...

Page 35: ...en the symbol and the configured value Figure 45 Figure 45 Analogue output configuration screen full scale value To edit the parameter press the button To modify the value of the selected digit press...

Page 36: ...en you see the option you want validate by pressing the button The unit goes back to the screen shown in Figure 46 To move to the next parameter on the menu press the button When the button is pressed...

Page 37: ...ESS DHB 424 model Screen to configure the unit s address on the Modbus network The screen flashes between the symbol and the configured value Figure 48 Figure 48 Modbus communications configuration sc...

Page 38: ...reset the unit to its default configuration The screen flashes between the symbol and the configured value Figure 51 Figure 51 Default configuration screens To edit the parameter press the button The...

Page 39: ...The unit will go back to the screen shown in Figure 52 To move to the next parameter on the menu press the button When the button is pressed the unit goes to the main screen of the services menu Figu...

Page 40: ...re 54 Figure 54 Unit of measurement display configuration screen To edit the parameter press the button The parameters that can be displayed are Unit of measurement LED off Unit of measurement LED on...

Page 41: ...back to showing the no option by default To move from one option to another press the button repeatedly When you see the option you want validate by pressing the button The unit goes back to the scre...

Page 42: ...al link speed of 9600 bauds DHB x24 B A GND RS 232 USB Ethernet Profibus PC RS 485 RS 485 RS 232 USB Ethernet Profibus DHB x24 1 8 9 10 1112131415 16 1 8 9 10 1112131415 16 29 30 31 32 33 34 35 36 29...

Page 43: ...a 16 bit record 7000 7039 float 32 bits Value given in two consecutive 16 bit records The records include the same data as the 32 bit records in the 7500 area Records valid for read function only 720...

Page 44: ...Value in two consecutive 16 bit records 2 Value in one 32 bit record 4 8 3 2 Configuration Regression of non linear equations parameters The Modbus address is in decimal format The read and write func...

Page 45: ...9999 7270 7271 7635 Address 1 1 Address 2 2 x8 Measured value for point no 8 19999 99999 7272 7273 7636 Address 1 1 Address 2 2 y8 Expected value for point no 8 19999 99999 7274 7275 7637 Address 1 1...

Page 46: ...1 Address 2 2 y17 Expected value for point no 17 19999 99999 7310 7311 7655 Address 1 1 Address 2 2 x18 Measured value for point no 18 19999 99999 7312 7313 7656 Address 1 1 Address 2 2 y18 Expected...

Page 47: ...ue Description 0 red 1 green 2 orange 4011 CoLbe Middle colour Value Description 0 red 1 green 2 orange 4012 CoLUp Upper colour Value Description 0 red 1 green 2 orange Address 1 1 Address 2 2 CoLLo L...

Page 48: ...Connection and disconnection delay Alarm 1 0 32400 s 4016 Led1 Alarm 1 LED Value Description 0 Interlocking of the alarm LED disabled 1 Interlocking of the alarm LED enabled Address 1 1 Address 2 2 P...

Page 49: ...1 n off 2 on 3 off 4 h on 5 h off 4023 dLy3 Connection and disconnection delay Alarm 3 0 32400 s 4024 Led3 Alarm 3 LED Value Description 0 Interlocking of the alarm LED disabled 1 Interlocking of the...

Page 50: ...bles Table 11 Modbus memory map Table 5 OUTPUTS DHB 424 Address Symbol Description 4029 p an Analogue output parameter Value Description 0 Input connected to the unit 1 Current time 4030 typa Type of...

Page 51: ...dress is in decimal format The read and write functions are enabled for all of these variables Table 12 Modbus memory map Table 6 SERVICES Address Symbol Description 4035 set Default configuration Val...

Page 52: ...ment error Bit8 Not used Bit7 Output board detected Bit6 Output board calibration error Bit5 Not used Bit4 Not used Bit3 Regression of non linear equations configuration error Bit2 Not used Bit1 Not u...

Page 53: ...d value Value currently being shown on the display 7012 7013 7506 current time Current time 7014 7015 7507 Wire resistance Cable resistance 7016 7017 7508 ADC ADC 7018 7019 7509 Terminal temperature T...

Page 54: ...nge Accuracy 1 Voltage input 0 10 V 10 10 V 0 1 Current input 0 20 mA 20 20 mA 0 1 Voltage input 60 mV 0 60 mV 0 1 Thermocouple type J 100 1200 C 0 1 Thermocouple type K 100 1370 C 0 1 Thermocouple ty...

Page 55: ...vironmental features Operating temperature 25 C 55 C Storage temperature 30 C 70 C Relative humidity with no condensation 25 95 Maximum altitude 2 000 m Protection degree Back IP10 Front panel IP65 Me...

Page 56: ...Figure 58 Dimensions of the DHB 4xx 56 DHB 402 DHB 424 Instruction Manual...

Page 57: ...roper installation or improper usage of the unit Consequently this guarantee does not apply to failures occurring in the following cases Overvoltages and or electrical disturbances in the supply Water...

Page 58: ...8 CE CERTIFICATE 58 DHB 402 DHB 424 Instruction Manual...

Page 59: ...Service Parameter error Error in configuration data The default configuration will be loaded as soon as any button is pressed The default parameters have been loaded To continue with the job press an...

Page 60: ...CIRCUTOR SA Vial Sant Jordi s n 08232 Viladecavalls Barcelona Tel 34 93 745 29 00 Fax 34 93 745 29 14 www circutor es central circutor es...

Reviews: