4�7�1�2�- COMPENSATION VALUE
Note:
Parameter applicable to temperature (RTD and Thermocouple) and resistance measurement in-
puts.
This configuration screen is used to select the compensation value.
For the RTD sensors this value is defined by the cable that joins the RTD sensor to the unit.
For the thermocouples it is defined by the
cold junction
.
The screen flashes between the symbol and the configured value. (
Figure 15: Compensation value screen�
To edit the parameter, press the
button.
To modify the value of the selected digit, press the
button repeatedly.
To jump to the next digit, press the
button.
Once at the desired value, validate by pressing the
button.
You can now select the position of the decimal point, which will be flashing.
To select the position of the decimal point, press the
button.
Validate by pressing the
button. The unit goes back to the screen shown in
To move to the next parameter on the menu, press the
button.
When the
button is pressed, the unit goes to the main screen of the input parameters menu (
Range:
RTD temperature or resistance measurement input
: 0 ... 20 Ω.
Thermocouple temperature input
: 0 ... 60ºC.
Note:
If a value is programmed that is out of range, the unit will activate automatic compensation.
Default value:
0.
4�7�1�3�- MEASUREMENT TIME
This screen lets you configure the measurement time for the input signal in seconds.
The screen flashes between the symbol and the configured value (
).
Figure 16:Measurement time display screen�
19
Instruction Manual
DHB-402 DHB-424