24
CVM-D41 DC
Instruction Manual
5�1�3�- CURRENT DISPLAY VALUE
This screen is used to configure the current value to display when the maximum value of the current
is input to the device.
75.00
A
Ct-1
Use the
, key to modify the value of the flashing digit
When the desired value is shown on the screen, press the
key to skip the digit.
When you reach the last digit and press the
key, you select the position of the decimal point.
Use the
to modify the decimal point.
Configuration values
Table 12: Configuration values: Current display value�
Current display value
Minimum value
1.000 A
Maximum value
9999
A
To validate the data, press the
key.
Use the
and
keys to browse the configuration screens of the menu.
5�1�4�- CURRENT INPUT
The shunt for the input current is selected on this screen.
75.00
Ct-2
mV
Use the
and
keys at the same time to configure the value.
Use the
key to browse the different options.
Configuration values
Table 13: Configuration values: Current input�
Current input
Possible values
50.00
(50.00 mV)
60.00
(60.00 mV)
75.00
(75.00 mV)
100.0
(100.0 mV)
150.0
(150.0 mV)
200.0
(200.0 mV)
250.0
(250.0 mV)
300.0
(300.0 mV)
400.0
(400.0 mV)
600.0
(600.0 mV)
To validate the data, press the
key.
Use the
and
keys to browse the configuration screens of the menu.