5�- TECHNICAL FEATURES
Power supply
Mode
Auxiliary
Rated voltage
CEM-C20 MID
CEM-C20
230 V ~
230 V ~ / 400 V ~
Tolerance
± 20 %
Frequency
50...60Hz
Consumption
< 2 W
< 10VA (In, Vref (without auxiliary services))
Voltage Measurement
Connection
Three-phase
Reference voltages
(according to version)
3x127/220 ... 3x230/400 V ~, 3x127/220 V~ or 3x230/400 V ~
Frequency (according to version)
50 Hz, 60 Hz or 50/60 Hz
Self-consumption of the voltage
circuit
< 2 W
< 10VA (In, Vref (without auxiliary services))
Current measurement (according to version)
Current (Ib / Iref)
5 A
10 A
Maximum current (Imax)
65A
60 A
Start-up current
0.04% of Itr
0.04% of Itr
Self-consumption of the current circuit
0.3 VA @ 10 A
0.3 VA @ 10 A
Itr
0.500 A
1.000 A
Ist
0.020 A
0.040 A
Imin
0.250 A
0.500 A
Maximum overcurrent time
( 30xImax) ( according to EN-50470-3)
50Hz
60Hz
50Hz
60Hz
½
cycle
½
cycle
½
cycle
½
cycle
Accuracy
Active Energy
CEM-C20 MID
CEM-C20
Class B (EN 50470)
Class 1 (IEC 62053-21)
Reactive Energy
Class 2.0 (IEC 62053-23)
Insulation
AC voltage
4kV RMS 50Hz during 1 minute
Overimpulse
1�2/50ms 0R source impedance
6 kV at 60º and 240º, with positive and negative polarization
Calculation and processing
Microprocessor
ARM
AD converter
16-bit
Impulse output
Type
Optocoupler
Operation
Emission of impulses proportional to the energy
Electrical features
Max. 24V 50mA
Impulse ON time
CEM-C20 MID
CEM-C20
40 ms
200 ms
No� of maximum impulses per second
12
31
Instruction Manual
CEM-C20