Invert
This parameter is used to select the phase whose filter is going to switch the current direction of the
load measurement transformer, so installation faults may be corrected.
Press the
key to save the modified settings.
7.10.- ALARMS
Note:
This screen is not visible on the
“slave”
devices.
In this screen,
, the enabling or disabling of the resonance alarm is selected.
Figure 64: Configuration screen: Alarms.
If the control algorithm was selected in the
Frequency mode
and this alarm is
enabled
, when the de-
vice detects a potential resonance on an harmonic, it disables said harmonic and generates an alarm,
but it continues filtering the rest of the harmonics.
If the alarm is
disabled
, the device may interpret a resonance as an overload and continue filtering the
harmonic.
This option is
enabled
by default and it is recommended not to disable it.
Before
disabling
the resonance alarm, it is essential to make sure there is no resonat-
ing current between the active filter and the load. Resonating currents can damage the
active filter and other devices connected to the installation.
Press the
key to save the modified settings.
Summary of Contents for AFQm IP54
Page 2: ...2 AFQm IP54...
Page 3: ...3 AFQm IP54 CONTENIDO CONTENTS MANUAL DE INSTRUCCIONES 4 INSTRUCTION MANUAL 89...
Page 86: ...86 AFQm IP54 Manual de Instrucciones ESPA OL 14 CERTIFICADO CE...
Page 87: ...87 Manual de Instrucciones AFQm IP54 ESPA OL...
Page 88: ...88 AFQm IP54 Manual de Instrucciones ESPA OL...
Page 171: ...171 Instruction Manual AFQm IP54 ENGLISH 14 CE CERTIFICATE...
Page 172: ...172 AFQm IP54 Instruction Manual ENGLISH...