EN
Pressure drops - clean filters:
CHILLED WATER
CW 40
CW 53
CW 78
CW 100
CW115
Flow rate (m
³
/h)
10 000
13 300
18 800
24 500
27 500
∆
P (Pa) G4/COARSE: 65 %
52
57
52
50
69
∆
P (Pa) F7/ePM1: 55 % (mm)
140
150
140
130
120
Filter fouling is measured by a pressure sensor located in the electrics box.
It is set to 1.5 times the value for the filter when clean (pressure ports upstream and downstream of the filter).
11.1.5 - Standard control elements:
(factory-wired)
-
Intake temperature sensor.
-
Differential pressure sensor: attached to the electrics box, this allows the difference in pressure upstream and downstream of
the filter to be measured, so as to determine whether the filter is fouled.
-
Water leak sensor: found at the end of a wound cable located at the bottom of the vertical unit so that it is long enough to extend
downwards into a raised floor, if required, and to be positioned in the area to be monitored.
It can be added on request.
11.2 - Optional components
11.2.1 - Heating coil
Moderately tighten the "coil supply" connections to avoid damaging the manifolds.
The coil is adjusted by a two-way or four-way valve equipped with a 0-10V servomotor (mounted and connected).
Coil specifications:
HOT WATER
CW 40
CW 53
CW 78
CW 100
Coil (1 row)
Number of coils
1
1
1
1
Capacity (l)
3,82
4,92
6,29
6,29
HEATING COIL
CW 40
CW 53
CW 78
CW 100
CW115
Nominal
Maximum
Nominal
Maximum
Nominal
Maximum
Nominal
Maximum
Nominal
Maximum
Air flow (m
³
/h)
10 000
13 300
13 300
13 300
18 800
20 500
24 500
27 000
27 000
27 500
Heating capacity (kW)*
36
40
44
44
63
66
71
73
Heating capacity (kW)**
18
21
23
23
33
34
37
38
* Conditions: return air 17 °C - 50 %, water temperature 80/60 °C
** Conditions: return air 17 °C - 50 %, water temperature 45/40 °C
Heating coil pressure drop*:
HOT WATER
CW
CW 40
CW 53
CW 78
CW 100
Nominal water flow rate (m
³
/h)
0,9
1,1
1,68
1,9
KV valve
4
4
4
4
∆
P Valve only (mWC)
0,6
0,8
1,8
2,3
∆
P (Pa) Valve + Coil (mWC)
1,5
1,8
3
3,8
Nominal flow rate :
water ∆T: 20 °C
CW40
CW53
CW78
CW100
KV
4
4
4
4
∆
P max.¹ Four-way valve
240
240
240
240
∆
P max.² Two-way valve
400
400
400
400
11 - TECHNICAL CHARACTERISTICS