6.3 Flow rates
(1) Heating mode with underground loop, indoor supply at 35°C, outdoor 0°C/-3°C
(2) Heating mode with ground water, indoor 30°C/35°C, outdoor 10°C/7°C
* If greater, install an additional or bigger expansion vessel
** in nominal mode 0/-3°C 30/35°C
GeoCIATTM Modular
20H
33H
45H(T)
Indoor sound power/pressure
dB(A) 45 / 23 46 / 24 47 / 25
Min. flow rates:
these flow rates must be observed. Failure to do so may lead to destruction of the exchanger due to
freezing. CIAT shall not be held liable for damage from frost caused by flow rates below the minimum rates specified
below.
Nominal flow rates:
these flow rates must be used to size all of the system's hydraulic components.
To keep your unit running at optimum performance, we recommend using the nominal flow rate.
6.2 Sound levels
Sound pressure level in HEATING mode at 5 metres, 1.5 metres from ground, in a free field, directivity 2.
6. SPECIFICATIONS
6.1 Technical specifications
GeoCIATTM Modular
20H
33H
45H
45HT
Compressor
Quantity
1
Type
hermetic scroll
Oil capacity (POE)
L
0,7
1,24
1,24
1,2
R410A charge
kg
1,25
1,35
1,25
1,25
Indoor heat
exchanger
Type
Brazed plate heat exchanger
Capacity
L
1,06
Indoor hydraulic
module
Expansion vessel capacity
L
10
Vessel inflation pressure
bar
1,5
Minimum water capacity of system
L
78
100
138
140
Max. water capacity (40°C) of the system
(pure water/glycol/water mix)*
L
250/176
Variable speed accelerator pump.
Operating pressure**
kPa
72,54
63,61
48,66
45,74
Outdoor heat
exchanger
Type
Brazed plate heat exchanger
Capacity
L
1,9
Outdoor hydraulic
module
Expansion vessel capacity
L
10
Expansion vessel inflation pressure
bar
1,5
Minimum water capacity of system
L
depends on catchment area
Max. water capacity of the system (pure
water/glycol/water mix)*
L
214
Variable speed accelerator pump.
Operating pressure**
kPa
57,8
50,9
32,9
24,4
GeoCIATTM Modular
20H
33H
45H(T)
Outdoor heat
exchanger
Minimum flow rate (m
3
/h)
0,7
0,85
1,2
Nominal flow rate, heating mode (1) underground
loop (m
3
/h)
1,4
1,7
2,4
Nominal flow rate, heating mode (2), ground water
(m
3
/h)
1,9
2,4
3,3
Indoor heat
exchanger
Minimum flow rate (m
3
/h)
0,5
0,65
0,85
Nominal flow rate, heating mode (m
3
/h)
1
1,3
1,7