11 TEST MODE
Test mode allows you to test the system by reducing the time the safety devices are activated.
This mode is activated by selecting the value YES in the setting field of the test mode sub-
menu in the Unit configuration menu. Test mode is valid for 1 hour.
Activating test mode results in the following:
- Cancellation of P190 and P191.
- Compressor short-cycle protection lowered to 1 minute.
- The 30-minute waiting period following a HP PRESSURE SWITCH fault (or EXT ECH FLUID SENSOR fault) is adjusted to match
the short cycle protection value.
- The heating element activation time delay is reduced from 80 seconds to 5 seconds.
12 OPERATING LIMITS
Heat pump heating mode
Indoor exchanger
water supply temperature (P281)
Outdoor exchanger
water supply temperature (P283)
-3°C
pure
water
-9°C
MPG
40%
P96 = +5°C
45°C
62°C
Operating zone
heat pump +
pure water
or
heat pump +
glycol/water mix
Additional
operating
zone
heat pump +
glycol/water
mix
0°C
MPG
20%
20°C
13 RADIO SIGNAL
The control terminal's radio signal reception level is shown at the bottom of the display.
Radio signal reception level satisfactory.
The control terminal is located too far from the heat pump.
The data sent to the heat pump may not be taken into
account.
Move the terminal closer to the heat pump to obtain the
optimal signal.
The control terminal is no longer communicating with the heat
pump. There is no longer a radio signal between the 2 pieces
of equipment. The message MACHINE COMMUNICATION
LOST appears on the home screen:
Move the terminal closer to the heat pump to obtain the
optimal signal.
UNIT CONFIGURATION
T
eST
mode
acTive
no
S
eTTing
:
YeS
COMMUNICATION LOST
MACHINE
gnd
fLoor
23.8
+
c
-----