EREBA ACCESS 17 - 40 T/HT
There follows a list of failures which might occur and their possible
causes and repairs.
In case the unit is not working properly, disconnect it from the mains
before trying to repair it.
Defect
Possible Cause
S
uggeSted
repair
The unit does not start
:
- Power supply disconnected;
connect
power
supply
.
- Main switch is cut-out;
cut
-
in
the
main
switch
.
-
Supply voltage too low;
check
supply
voltage
.
-
Triggering of a protection device;
reset
the
protection
device
.
- Blocked contactor;
check
and
replace
the
blocked
contactor
if
necessary
.
- Seizing of compressor;
check
and
replace
compressor
if
necessary
.
- Loose electric connections;
check
and
tighten
the
electric
connections
.
The unit works continuously or cycles too often:
- Failure of compressor contactor;
check
and
replace
contactor
if
necessary
.
- Compressor failure;
check
and
replace
compressor
if
necessary
.
- Refrigerant leak;
check
the
charge
and
add
more
refrigerant
.
- Water flow is insufficient;
check pressure loss in the water circuit.
- Static pressure in water circuit is insufficient;
check it on the pressure gauge and restore it if necessary.
The unit stops because of low pressure alarm:
- Refrigerant leak;
check
the
charge
and
add
more
refrigerant
.
- Water flow in the heat exchanger is insufficient;
check
the
water
pump
.
- Unit starting delay;
wai
t
until
the
system
is
stable
.
The unit stops because of high pressure alarm:
- Failure of high pressure switch;
check
and
replace
pressure
swi
tch
if
necessary
.
- The expansion valve is blocked;
check
and
replace
the
expansion
valve
if
necessary
.
- Dehydrating filter clogged;
check
and
replace
filter
if
necessary
.
- Outdoor fan/s not working;
check
the
fans
/
s
motor
/
s
and
its
electric
connections
.
-
Coil clogged or dirty;
remove clogging or clean the coil.
The unit is too noisy:
- Piping vibration;
fix
the
pipes
properly
.
- The compressor is too noisy;
check
and
replace
compressor
if
necessary
.
- The expansion valve blows;
check
the
charge
and
add
refrigerant
if
necessary
.
- Panels are not installed correctly;
install
the
panels
properly
.
Oil leak from the compressor:
- Leaks from the refrigerant circuit;
find
and
repair
leaks
.
Water leaks:
- Defects at inlet and/or outlet water connections;
check
and
tighten
connections
if
necessary
.
The defrost system of the unit is not working (only on units EREBA
ACCESS HT):
- Failure of 4-way backflow valve;
check
and
replace
valve
if
necessary
.
- Defrost probe is not working;
check
and
replace
probe
if
necessary
.
13 - TROUBLESHOOTING
Summary of Contents for EREBA ACCESS 17-40 T/HT
Page 1: ...EREBA ACCESS 17 40 T HT 11 2017 X0178 Instruction manual...
Page 2: ......
Page 113: ...RU RU 111 NR 17 19 A 5 70 o C R 410A CIAT 0 C 300 2...
Page 114: ...NR 17 19 A RU 112 10 15 CIAT 7511632 17 21 7511634 26 40 16 26 40 I 26 40 1 2 15...
Page 121: ...RU RU 119 NR 17 19 A 26 40 6 9...
Page 126: ...NR 17 19 A RU 124 II II 5 5 1 5 100 C 15 C RTPF AFNOR X60 010 12...
Page 127: ...RU RU 125 NR 17 19 A 1 2 X X X X X X 1 EN 378 3 2 1 EN 378 1 CIAT CIAT EN 378 4 1 1 EN 378...
Page 128: ...NR 17 19 A RU 126 EREBA ACCESS HT 4 13...
Page 129: ......