EREBA ACCESS 17 - 40 T/HT
EN - 16
Minimum and maximum water flow rates in the
plate heat exchangers
Minimum flow rate, l/s
Maximum flow rate
(1)
, l/s
EREBA ACCESS 17 T
0.40
1.39
EREBA ACCESS 17 HT
0.45
1.39
EREBA ACCESS 21 T
0.47
1.52
EREBA ACCESS 21 HT
0.57
1.52
EREBA ACCESS 26 T
0.63
1.96
EREBA ACCESS 26 HT
0.67
2.18
EREBA ACCESS 33 T
0.82
2.18
EREBA ACCESS 33 HT
0.87
2.29
EREBA ACCESS 40 T
0.99
2.60
EREBA ACCESS 40 HT
1.05
2.60
(1) Maximum water flow rate with an available static pressure of 50 kPa (units with
hydraulic module)
Water circuit water content
Whatever the size of the system, the minimum content of the water circuit
is given by the following formula:
Content = CAP
(kW)
x N = Litres
where CAP is the nominal system capacity (kW) at nominal operating
conditions of the installation.
Application N
Air conditioning
3.5
Industrial process cooling
See note