8 - ELECTRICAL CONNECTIONS

 Before connecting the unit to the mains, ensure that the voltage matches that given on the unit's name plate  

(230 V - 50 Hz for single-phase and 400 V - 50 Hz for three-phase). The unit must be connected to earth.

CIAT shall not be liable for incidents resulting from faulty or non-existent earthing.

• 

H4000 Heliotherme and TPL4000 Destratifier:

 

-

Direct connection to AC Single-Phase and AC Three-Phase fan motor assembly

 

-

Diagram 7168208

• AC single-phase fan motor assembly

 

-

1 Ph/230 V AC motor + proximity  RTR thermostat connection --> Diagram 7528218

 

-

1 Ph/230 V AC motor + proximity  AC thermostat connection --> Diagram 7528219

• HEE single-phase fan motor assembly

 

-

1 Ph/230 V EC motor + proximity  EC 3-speed thermostat connection --> Diagram 7528220

 

-

Direct connection --> Diagram 7423956

 

-

Heliotherme 1 Ph/230 V EC motor + HEE 1-PHASE BOX wiring diagram --> Diagram 7400559

 

-

Heliotherme 1 Ph/230 V EC motor + HEE 1-PHASE BOX field connection --> Diagram 7400560

• AC three-phase fan motor assembly

 

-

Schematic diagram 2-speed in MAN → Diagram 7272770

 

-

Schematic diagram 2-speed in AUTO → Diagram 7113020

• With electric heater (EH)

 

-

Fan-controlled operation

The operation of the heating coil must be fan-controlled. Power to the electric heating elements must be cut whenever the fan 

motor assembly is stopped intentionally or unintentionally.
It is essential to ensure that a time delay is set up so that the fan is only allowed to stop after the power to the coil is cut (post-

ventilation) (minimum 180 seconds).

• Protection against overheating

This is provided by 2 temperature limit thermostats (AUTO & MAN)

These must always be positioned at the top (which means that the electrical connection must be positioned to the left when looking 

at the unit from the front, opposite the supply air).
It is important to ensure that the operation of the electric coils is controlled by the safety thermostat cut-out.

 

-

Schematic diagram for 2-stage coil with 3-PHASE fan motor assembly → Diagram 5952024

 

-

Schematic diagram for 3-stage coil with 3-PHASE fan motor assembly → Diagram 5952018

 

-

Schematic diagram with ECO+ ELEC BOX --> Diagram 7227323

H4000 HELIOTHERME 

EN-12  

Summary of Contents for DESTRATIFIER TPL 4000

Page 1: ...H4000 HELIOTHERME DESTRATIFIER TPL 4000 06 2019 EN7512234 03 Instruction manual...

Page 2: ...H4000 HELIOTHERME EN 2...

Page 3: ...H4000 Heliotherme 9 6 2 TPL4000 Destratifier 9 6 3 Wall mounted H4000 Heliotherme 9 6 4 Ceiling mounted H4000 Heliotherme 10 7 WATER CONNECTIONS 11 7 1 Connection to be tightened HELIOTHERME LP Water...

Page 4: ...er must provide the exact number of parcels delivered If any damage is found upon delivery describe the damage observed on the delivery receipt in the presence of the delivery driver before the delive...

Page 5: ...TPL4500 HS 1391 rpm 1 51 A 770 W LS 1176 rpm 0 90 A 520 W H4630 TPL4630 HS 870 rpm 1 30 A 590W LS 750 rpm 0 63 A 250 W H4630S HS 870 rpm 1 30 A 590W LS 750 rpm 0 63 A 250 W 3 2 CORROBLOC fan motor ass...

Page 6: ...54 TACH B 25 C 60 C H4400 TPL4400 1760 rpm 2 2 500 55 NC 250 VAC 2 A F 25 C 60 C H4450 TPL4450 1500 rpm 2 2 500 55 NC 250 VAC 2 A F 25 C 60 C H4500 TPL4500 970 rpm 1 1 250 55 NC 250 VAC 2 A F 25 C 60...

Page 7: ...4 42 4 42 4 Connection type Smooth 316L stainless steel to be welded Maximum operating pressure 16 bar Test pressure 24 bar Max T 200 C 4 3 High Pressure Steam Coil HPSC 316L stainless steel tube Alum...

Page 8: ...1 142 142 142 142 126 E 126 126 143 143 188 200 Weight kg 1 row 21 30 40 50 62 60 2 rows 18 24 32 42 53 67 3 rows 26 34 44 56 72 E HEE FMA A B D C E 5 2 TPL4000 Destratifier Size TPL40 TPL45 TPL50 TPL...

Page 9: ...nes you are recommended to position DESTRATIFIERS at a height of Between 5 and 15 metres The rear of the unit must be at least 145 mm from the wall to facilitate removal of the fan motor assembly when...

Page 10: ...et nuts to lock the assembly in place 5 Fix the HELIOTHERME unit using the 4 x H M8 x 50 screws supplied with the wall bracket Size 4300 4350 4400 4450 4500 4630 4630S Distance mm 512 558 610 710 808...

Page 11: ...caps are protected from the excessive heat produced during welding by using a damp cloth when welding between the HELIOTHERME and the supply pipes Welding must be carried out according to good working...

Page 12: ...C three phase fan motor assembly Schematic diagram 2 speed in MAN Diagram 7272770 Schematic diagram 2 speed in AUTO Diagram 7113020 With electric heater EH Fan controlled operation The operation of th...

Page 13: ...direction The flow rate or the water temperature supplied by the HELIOTHERME is not sufficient See the information on the Switching on page Refer to the pages on Heat air and sound performance relati...

Page 14: ...cessories return diffusion modules Wall bracket and Additional IPN kit Ceiling bracket Model Wall bracket product code Additional IPN kit product code Assembly diagram Model Code Assembly diagram H430...

Page 15: ...r frost protection thermostat kit or 100 recirculated air Adjust the fresh air rates in your building to meet prevailing requirements or based on room occupancy levels built in timer Make wise use of...

Page 16: ...its to be controlled one HEE BOX master or slave unit controls 6 HELIOTHERME units or 3 HELIOTHERME units 3 TPL The display shows the operating status of each individual HELIOTHERME unit fresh air or...

Page 17: ...B C D E F G H Connection diameter X Y Z H4300 600 395 286 506 115 0 290 52 G 1 2 union 260 340 110 H4350 646 459 286 506 100 53 357 51 G 3 4 union 310 390 110 H4400 700 555 286 506 100 53 451 52 G 3...

Page 18: ...n the unit 4 Refit the 4 x M8 screws in their original positions to secure the filter box in place 5 Refit the galvanised mesh filter held in place by the 2 brackets and the 2 butterfly screws Filter...

Page 19: ...secure the guard plate B on the diffuser C 3 Place the diffuser support against the Heliotherme and secure it using the CBLX screws supplied D 4 Refit the guard plate B and secure it with the CBLX scr...

Page 20: ...secure the grille B on the support C 3 Place the diffuser support against the Heliotherme and secure it using the CBLX screws supplied D 4 Refit the grille B and secure it with the CBLX screws A 5 Fit...

Page 21: ...assembled and contaminated fluids removed by professionals and processed via approved channels for electrical and electronic equipment WEEE In France CIAT has formed a partnership with ECOLOGIC for th...

Page 22: ......

Page 23: ......

Page 24: ...ciat com Compagnie Industrielle d Applications Thermiques Corporation with a capital of 26 728 480 R C S Bourg en Bresse B 545 620 114 This document is not legally binding As part of our continuous d...

Reviews: