AlarmText
Text description of current alarm
Text description of alarm
Read-only
119
InfoEnergyDemandAC
Cold water demand from master to slave by positioning of
actuators
values of 0 to 255%
Read-only
120
InfoEnergyDemandAH
Hot water demand from master to slave by positioning of
actuators
values of 0 to 255%
Read-only
121
InfoEnergyDemandAir
Fresh air demand from master to slave by positioning of
actuators
0 or 100%
Read-only
122
ActPosSetpHeatStageA
Heating valve control from master to slave by positioning of
actuators
Values of 0 to 100%
Read-only
123
ActPosSetpHeatStageB
Electric heater control from master to slave by positioning of
actuators
Values of 0 to 100%
Read-only
124
ActPosSetpCoolStageA
Air conditioning valve control from master to slave by positioning
of actuators
Values of 0 to 100%
Read-only
125
FanSpeedSetp
Ventilation control from master to slave by positioning of
actuators
Values of 0 to 100%
Read-only
126
ActPosSetpFreshAir
Fresh air control from master to slave by positioning of actuators
0 or 100%
Read-only
127
InfoEnableHeat
Enable heating from master to slave by enabling heating/cooling
mode
0 = Disabled/1= Enabled
Read-only
128
InfoEnableCool
Enable air conditioning from master to slave by enabling
heating/cooling mode
0 = Disabled/1= Enabled
Read-only
HMI
129
TempRoom
CIAT terminal ambient temperature
Temp. value in °C
Read-only
130
TempRoomSetpUserOffset Comfort setpoint override via CIAT terminal
Temperature shift value in K
Read-only
131
ComfortPushButton
On/Off control via CIAT terminal
0 = Reduced (Stdby/Eco/Frost
protection)/1=Comfort
Read-only
132
FanSpeedUser
Manual speed selected via CIAT terminal
Values of 0 to 100% LS 33% MS 66% GS
100%
Read-only
133
FanManual
Auto/Man. speed selection on CIAT terminal
0=Auto/1=Man.
Read-only