ActPosSetpHeatStageA
Heating valve control from master to slave by positioning of
actuators
Values of 0 to 100%
Write only
29
ActPosSetpHeatStageB
Electric heater control from master to slave by positioning of
actuators
Values of 0 to 100%
Write only
30
ActPosSetpCoolStageA
Air conditioning valve control from master to slave by positioning
of actuators
Values of 0 to 100%
Write only
31
FanSpeedSetp
Ventilation control from master to slave by positioning of
actuators
Values of 0 to 100%
Write only
32
ActPosSetpFreshAir
Fresh air control from master to slave by positioning of actuators
0 or 100%
Write only
33
InfoEnableHeat
Enable heating from master to slave by enabling heating/cooling
mode
0 = Disabled/1= Enabled
Write only
34
InfoEnableCool
Enable air conditioning from master to slave by enabling
heating/cooling mode
0 = Disabled/1= Enabled
Write only
35
WindowSwitch
Synchronisation input for master/slave window switches
0 = Closed/1 = Open
Write only
36
EnergyDemandAC or
DemAC ?
Cold water demand expressed in %
values of 0 to 255%
Read-only
37
EnergyDemandAH or
DemAH ?
Hot water demand expressed in %
values of 0 to 255%
Read-only
38
EnergyDemandeAir or
DemAir
Fresh air demand expressed in %
0 or 100%
Read-only
39
ActPosHeatStageA
Information on state of heating valve position in %
Values of 0 to 100%
Read-only
40
ActPosHeatStageB
Information on state of electric heater position in %
Values of 0 to 100%
Read-only
41
ActPosCoolStageA
Information on state of air conditioning valve position in %
Values of 0 to 100%
Read-only
42
FanSpeed
Information on state of fan speedin %
Values of 0 to 100%
Read-only
43
ActPosFreshAir
Information on state of fresh air damper position in %
0 or 100%
Read-only
44
CoilConsumptionAC
Cold water coil consumption in kWh
Cold water coil consumption in kWh
Read-only
45
CoilConsumptionAH
Hot water coil consumption in kWh
Hot water coil consumption in kWh
Read-only
46
ElectricConsumption
Electric heater consumption in kWh
Electric heater consumption in kWh
Read-only
47
FanConsumption
Fan motor consumption in kWh
Ventilation consumption in kWh
Read-only
48
TempReturnAir
Return air temperature
Temp. value in °C
Read-only
49
TempDischargeAir
Supply air temperature
Temp. value in °C
Read-only
50
TempFlowWater
Water temperature (local changeover)
Temp. value in °C
Read-only
51
InfoOnOff
Information on state of synchronised output
0 = OFF/1 = ON
Read-only
52
OnOff
On/Off control of switch wired to controller
0 = OFF/1 = ON
Read-only
53
InAlarm
Controller alarm
0 = No Alarm / 1 = Alarm
Read-only
54
AlarmInfo
Error code of current alarm
Error code
Read-only
55
AlarmText
Text description of current alarm
Text description of alarm
Read-only
56
WindowSwitch
Synchronisation output for master/slave window switches
0 = Closed/1 = Open
Read-only