VII / USER SETTINGS:
No.
Description
Possible choices
00
Operating mode
Used to set the control
box's operating mode
Unit
-
WintEr
(used for heating)
SuMMEr
(used for cooling)
Auto
(reversible), usable only if the optional
changeover thermostat is fitted to the coil's main
Min.
-
Max.
-
00
changeover thermostat is fitted to the coil s main
supply pipe. It will automatically enable WINTER or
SUMMER mode, depending on the temperature of the
fluid
.
Max.
Default
WintEr
Increment
-
01
Override
:
Allows the user to override
the control mode being
used
Unit
-
Off
CFt
(Comfort)
ECO
(Economy)
Min.
-
Max
-
01 used
ECO
(Economy)
H.GL
(Frost Protection)
tiMe
(depending on time schedule)
Max.
Default
CFt
Increment
-
Temperature
setpoint
in
WINTER
mode
Unit
°C
Min.
0
S tti
03
02
0 to 51°C
Max.
Setting 03
– 0.2°C
Default
18
Increment
0.2
Temperature
setpoint
in
Unit
°C
Mi
Setting 02
03
p
p
SUMMER
mode
0 to 51°C
Min.
g
+ 0.2°C
Max.
51
Default
18
Increment
0.2
Ventilation
:
Unit
-
Auto
(LS or HS selected based on the difference
04
Used for overriding the air
speeds of the
HELIOTHERME units
between the temperature setpoint entered (WINTER
or SUMMER) and the indoor temperature measured).
SPeedL
(3-ph motor low speed)
SPeedH
(3-ph motor high speed)
If a speed is overridden, the duration of the override is
set by parameter 27.
Min.
-
Max.
-
Default
AUTO
Increment
-
10