V / ELECTRICAL CONNECTIONS:
Diagram 7227322 page 16
(control: air and/or water or fresh air)
One 3-phase HELIOTHERME 4000 unit driven by one 3-PH Eco+ BOX slave unit
Communication between the slave units
:
Setpoint signals are sent between slave units via
terminals
20
and
21
on the internal controllers.
Master controller power supply
:
The 3-PH Eco+ BOX slave unit delivers 12 V to the
master controller via terminals
18
and
19
. The master
controller must be connected to the
S
and
12 V
terminals.
Slave unit network power supply
:
Connect the 3-ph/400 V supply with N and PE to the
disconnect switch Q1 between
1-3-5-7-PE
.
Communication between the master controller and
the 3-PH Eco+ BOX slave unit:
The setpoint signals are sent by terminals
A
and
B
on
the master controller. The slave unit receives these
setpoint signals on terminals
20
and
21
on the internal
controller.
Room sensor
:
The sensor head is prewired to the control box (
T°C
)
and attached to the cable gland on the hinged side.
Optional 15 m remote sensor (code 7207381). This
remote sensor may be connected to terminals
22
and
23
th
l
it
Motor overload protection
:
Connect the fan motor assembly's overload protection to
terminals
3
and
4
on the slave unit.
23
on the slave unit.
Three-phase fan motor assembly
:
Before attempting to wire the connections, ALWAYS remove the jumper strips in the fan motor assembly's terminal box.
This will ensure that the control will operate correctly and that the fan motor assembly will run in the correct order.
Wire to motor contactors
KVL1
and
KVP1
. The choice between the star (LS) or delta (HS) configuration will be selected
automatically based on the difference between the indoor temperature measured and the temperature setpoint(s)
entered.
Valve actuator
:
(
ti
i
l d d i th 0 10 V
l
kit)
Frost protection thermostat
(
ti
7228902 i
l d d i f
h i kit B400414)
(option included in the 0-10 V valve kit)
Supplies water to the heat exchanger in proportion to
the building's heat requirements.
The valve actuator's 24 V power supply is delivered by
terminals
9
and
10
on the 3-PH Eco+ BOX slave unit.
The 0-10 V control signal is delivered by terminal
11
on
the 3-PH Eco+ BOX slave unit.
(option 7228902 included in fresh air kit B400414)
Place the frost protection thermostat's bulb inside the 2-
channel mixing box with built-in filter. This component of
the optional fresh air kit will enable you to draw fresh air
indoors whilst preventing frost from forming on the heat
exchange coil.
Connect terminals
1
and
4
on the thermostat to terminals
1
and
2
, respectively, on the 3-PH Eco+ BOX slave unit.
Fresh air/return air mixing box damper actuator
(option 0816423 included in fresh air kit B400414)
Install the damper actuator on the telescopic linkage on the
CIAT 2-channel mixing box with built-in filter. The damper's
minimum and maximum opening and closing positions are
adjusted mechanically. A spring returns the damper to its
initial position. This component of the optional fresh air kit
Changeover thermostat
(option 7128892)
Thermostat to be mounted on the water supply pipes
of each HELIOTHERME heat exchanger. Required for
automatic
changeover
between
WINTER
(open
contact) and SUMMER (closed contact) modes.
Connect the changeover thermostat's white wire to
p
p
p
will enable you to draw fresh air indoors whilst preventing
frost from forming on the heat exchange coil.
Connect terminals
1
and
2
on the damper actuator to
terminals
7
and
8
, respectively, on the 3-PH Eco+ BOX
slave unit.
g
terminal
5
on the 3-PH Eco+ BOX slave unit and the
black wire to terminal
6
on the 3-PH Eco+ BOX slave
unit
.
6