Setting
No.
Description
Setting
value
Factory
setting
00
Unit version
1 = AQUALIS
2 = AQUALIS 2
2
01
Glycol content
0 = pure water
1 = glycol/water mix
0
02
On/Off input on
J2, terminals 3-5
0 = input not used
1= input used to force heating and cooling modes
2 = input used to place unit in frost protection mode by remote control
0
03
Heating terminal units
0 = radiators/fan coil units or combined with floor (TU)
1 = radiant floor heating and cooling system (RFHC)
1
04
Ambient temperature
compensation factor
0 to 5
2
05
Low-noise
operation
0 = Standard
1 = Low noise in cooling mode
2 = Low noise in heating mode
3 = Low noise in cooling and heating modes
2
06
Auxiliaries
and bypass possibilities
0 = heat pump only (bypassing of heat pump possible)
1 = heat pump + electric auxiliary units (bypassing of auxiliaries possible)
2 = heat pump + electric auxiliary units (bypassing of heat pump and terminals
possible)
3 = heat pump or boiler backup (bypassing of heat pump possible)
4 = heat pump or boiler backup (bypassing of heat pump and boiler possible)
5 = heat pump + boiler backup (bypassing of heat pump possible)
0
07
Outdoor temperature
for auxiliary authorisation
P9 at 24°C
5°C
08
Compressor confirmation
0 = compressor not authorised to run
1 = compressor authorised
1
09
Heating
low limit (air)
-15°C to 24°C
-15°C
TU
RFHC
TU
RFHC
10
Water comfort setpoint
in cooling mode
10°C to 28°C if P1 = 0
-6°C to 28°C if P1= 1
20°C to 25°C if P22 = 0 or 1
18°C to 25°C if P22 = 2 or 3
12°C
23°C
11
Water economy setpoint
in cooling mode
10°C to 28°C if P1 = 0
-6°C to 28°C if P1= 1
20°C to 25°C if P22 = 0 or 1
18°C to 25°C if P22 = 2 or 3
12°C
23°C
12
Outdoor air temperature at start
of drift in cooling mode
10°C to 40°C
empty
25°C
empty
13
Outdoor air temperature at end
of drift in cooling mode
P12+5°C to 45°C
35°C
14
Maximum setpoint at end
of drift in cooling mode
10°C to 28°C if P1 = 0
-6°C to 28°C if P1= 1
15°C
15
Water comfort setpoint
in heating mode
20°C at P19
30°C
20°C
16
Water economy setpoint
in heating mode
20°C at P19
30°C
20°C
17
Outdoor air temperature at start
of drift in heating mode
-10°C to 30°C
17°C to 25°C
20°C
20°C
18
Outdoor air temperature at end
of drift in heating mode
-15°C to P17-5°C
-15°C to 8°C
-7°C
-7°C
19
Maximum setpoint at end
of drift in heating mode
20°C to 49°C if P06 = 0,
20°C to 55°C if P6 = 1 or 2
20°C to 70°C if P6 = 3, 4 or 5
20°C to 40°C
40°C
35°C
20
Stage differential
0.5°C to 10°C
2°C
21
Interstage differential
0.5°C to 10°C
2°C