Setting
No.
Description
Setting
value
Factory
setting
22
Pool
and humidity sensor options configura-
tion
0 = no pool or humidity sensor options
1 = pool management
2 = humidity sensor management
3 = pool + humidity sensor management
0
23
Pool water setpoint
20°C to 35°C
28°C
24
Self-regulating frosting time
0
= No
1
= Yes
0
25
Temperature of time-delay coil
before defrosting
-5 to 0°C
-2°C
26
Minimum water return
defrosting authorisation
TU
25°C if P1=0
10°C if P1 = 1
RFHC
20°C if P1=0
5°C if P1 = 1
20°C
27
Defrosting end temperature
10 to 45°C
35°C
28
Frosting time
10 to 90 min.
30 min.
29
Compressor stop at end of defrosting
0 = not stopped
1 = 3-minute stop
0
30
Test mode
0 = No / 1 = Yes
0
31
Frost protection mode setpoint
8 to 15°C air setpoint
10°C
32
Maximum freon temperature change
Exchanger for frost protection
0°C to 5°C
1 °C
33
Maximum temperature change
Water outlet for frost protection
0°C to 1°C
0.3 °C
34
Circulator operation
control
0 = stopped if boiler on
1 = continuous operation
1
36
Cooling mode authorisation
0 = Cooling mode inhibited
1 = Cooling mode authorised
1
40
Water return temperature
Value read
41
Water supply temperature
Value read
42
Calculated water setpoint
Value read
43
Corrected stage differential
Value read
44
Freon temperature in outdoor coil
Value read
45
Freon temperature in exchanger
Value read
46
Short-cycle protection time delay
Value read
47
Remaining frosting time
Value read
48
Outdoor temperature
Value read
49
Fault reset number counter
Value read
50
Pool temperature
Value read
60
Domestic hot water
production option
0 = heating/cooling output
1 = heating of domestic hot-water tank with one cycle per day
2 = heating of domestic hot-water tank with two cycles per day
0
61
Cycle 1 start time
domestic hot water
Adjustable to between 0:00 and 23:30
1:30
62
Cycle 2 start time
domestic hot water
Adjustable from P61 + 6 hours to 23:30
12:30
63
Maximum duration of DHW when heat
pump operating in heating mode
30 min. to 2 hours (adjustable)
2 hours
80
Control card version number
Value read
81
Terminal version number
Value read
93
Exchanger frost protection limit
on water supply
Fixed at +3°C for pure water: P1 = 0
Adjustable between -10°C to and +3°C for glycol/water mix: P1 = 1
+3°C if P1 = 0
0°C if P1 = 1
94
Freon exchanger frost protection limit
empty
P93 - 5°C
95
High limit, exchanger water return
in cooling mode
empty
40°C
96
High limit, exchanger water return
in heating mode
empty
10°C if P1 = 0
5°C if P1 = 1
98
Refrigerant used
1 = R410A
1
99
Cooling only/reversible version
0 = Cooling only
1 = Reversible
Depending on
your
Aqualis 2