FLOWAY “Classic PHE” and "Classic RHE/RHE-Z"
Sizes
1000
2000
3000
4000
5000
6000
7500
10 000
2 rows
15 000
2 rows
Ø connections
(mm) 4-way valve
inlet
G 1/2"
G 1/2"
G 3/4"
G 3/4"
G 3/4"
G 1"
G 1"
G 1"1/2
G 1"1/2
outlet (on valve)
G 1/2"
G 1/2"
G 3/4"
G 3/4"
G 3/4"
G 1"1/2
G 1"1/2
Rp 1"1/4
Rp 1"1/4
Sizes
10 000
4 rows
15 000
4 rows
Ø connections (mm) 3-way valve
inlet
G2"
G2"
outlet (on valve)
Rp 1"1/2
Rp 1"1/2
sVertical FLOWAY PHE
Sizes
700
1500
2000
Ø connections (mm) 4-way valve
Valve inlet
G 1/2"
G 1/2"
G 1/2"
Valve outlet
G 1/2"
G 1/2"
G 1/2"
ELECTRICAL CONNECTIONS
FLOWAY “Classic PHE” and "Classic RHE/RHE-Z"
Sizes
1000
2000
3000
4000
5000
6000
7500
10000
15000
Supply type
1~230 V
- 50 Hz
3~400 V - 50 Hz
Nominal current without internal electric heater (A)
5,8
4,2
7
8,6
8,6
10
10
19
24,6
Minimum power supply cable section without electric
heater*
1,5 mm² 1,5 mm² 1,5 mm² 1,5 mm² 1,5 mm² 1,5 mm² 1,5 mm² 2,5 mm² 2,5 mm²
Disconnect switch size
OT40(40A)
Nominal current with internal electric heater (A)
25,4
19,8
25,2
32,8
37,2
42,9
55
91,2
118,4
Minimum power supply cable section with electric heater*
2,5 mm² 2,5 mm² 2,5 mm² 4 mm²
6 mm²
6 mm²
10 mm²
25 mm² 35 mm²
Disconnect switch size
OT40 (40 A)
OT40
(40 A)
OT40
(40 A)
OT63
(63 A)
OT63
(63 A)
OT63
(63 A)
OT80
(80 A)
OT100
(100 A)
OT125
(125 A)
Max. terminal section (mm²)
10 mm²
10 mm²
10 mm²
35 mm²
35 mm²
35 mm²
35 mm²
70 mm²
70 mm²
Torque Value (N.m)
0,8 Nm
0,8 Nm
0,8 Nm
2 Nm
2 Nm
2 Nm
2 Nm
6 Nm
6 Nm
Vertical FLOWAY PHE
Sizes
700
1500
2000
Supply type
1~230 V - 50 Hz
3~400 V - 50 Hz
Nominal current without internal electric heater (A)
6,2
4,2
4,2
Minimum power supply cable section without electric heater*
1,5 mm²
1,5 mm²
1,5 mm²
Nominal current with internal electric heater (A)
25,8
15,9
19,8
Minimum power supply cable section with electric heater*
2,5 mm²
1,5 mm²
2,5 mm²
Disconnect switch size
OT40 (40 A)
OT40 (40 A)
OT40 (40 A)
Max. terminal section (mm²)
10 mm²
10 mm²
10 mm²
Torque Value (N.m)
0,8 Nm
0,8 Nm
0,8 Nm
* The minimum cable sections are given as a guideline for a JZ type cable at 30 °C in the open air (outside the duct).
These sections must be calculated taking into account the specifications of each installation (type of fitting, ambient temperature,
cable length etc.)
5 – INSTALLATION AND INSTALLATION CONNECTIONS
FLOWAY EN-24