4.3 - TECHNICAL CHARACTERISTICS
Air flow rates
Floway “Classic PHE”
Size
"Classic PHE"
Minimum flow rate (m³/h)
Nominal flow rate (m³/h)
Maximum flow rate (m³/h)
1000
300
1000
1200
2000
500
2000
2200
3000
700
3000
3700
4000
900
4500
5100
6000
1400
6000
6600
Operating limit temperature: -20°C/+ 60°C with preheating coil
Floway "Classic RHE/RHE-Z"
Size
"Classic RHE/RHE-Z"
Minimum flow rate (m³/h)
Nominal flow rate (m³/h)
Maximum flow rate (m³/h)
Maximum flow rate without
cooling coil (m³/h)
1000
300
1000
1200
1450
2000
500
2000
2500
2800
3000
700
3000
3700
4500
4000
900
4500
5700
5700
5000
900
5000
5700
7000
6000
1400
6000
8500
8500
7500
1400
7500
8500
11000
10 000
2500
10 000
14 000
14000
15 000
3000
15 000
18 000
18000
Operating limit temperature: -30°C/+ 60°C
Vertical FLOWAY PHE
Size
Minimum flow rate (m³/h)
Nominal flow rate (m³/h)
Maximum flow rate (m³/h)
700
300
700
1200
1500
700
1500
2000
2000
700
2000
2600
Operating limit temperature: -20°C/+ 60°C with preheating coil
4 - DESCRIPTION OF THE UNIT & TECHNICAL CHARACTERISTICS