9 - NOMINAL SYSTEM WATER FLOW CONTROL
9.1 - General
The water circulation pumps of the TD units have been sized to
allow the hydraulic modules to cover all possible configurations
based on the specific installation conditions, i.e. for various
temperature differences between the entering and the leaving
water (∆T) at full load, which can vary between 3 and 10 K. This
required difference between the entering and leaving water
temperature determines the nominal system flow rate.
The pump of the hydraulic module is a variable speed pump.
Two different water flow control can be selected:
•
fixed speed control
• variable speed control based on constant temperature
difference.
Default factory setting is fixed speed. Settings change need to
be done by a CIAT Service representant.
For both flow control and for energy saving, the speed of the
pump will be reduced to its minimum when unit capacity is 0%.
It is essential to know the nominal system flow rate to be able to
control it, using the variable pump speed or a manual valve that
must be on the water leaving piping of the system (item 20 in
the typical hydraulic circuit diagram).
The flow control with the pump speed or with the valve permits
adjustment of the pressure/system flow rate curve in accordance
with the pump pressure/flow rate curve to obtain the nominal
flow rate at the required operating point (see example for unit
size TD 035). The pressure drop reading in the plate heat
exchanger is used as means of control and adjustment of the
nominal system flow rate. This reading can be taken with a
differential pressure gauge that must be installed at the heat
exchanger inlet and outlet.
Use the specifications of the unit selection to know the system
operating conditions and to deduce the nominal flow rate and
the plate heat exchanger pressure drop at the specified
conditions. If this information is not available at the system start-
up, contact the technical service department responsible for the
installation to get it.
These characteristics can be obtained with the Electronic
Catalogue selection program for all ∆T conditions in the range
of 3 to 10 K.
For domestic hot water applications (leaving water temperatures
above 60°C) the control cannot be made at a ∆T below 8 K at
the condenser.
9.2 -
Water flow control procedure (fixed
speed)
Hydraulic circuit cleaning procedure
-
Open the valve fully (item 20) if present.
-
Start-up the system or unit pump (by quick test).
-
Read the plate heat exchanger pressure drop by taking the
difference of the readings of the pressure gauge connected
to the unit inlet and outlet (item 19).
-
Let the pump run for two consecutive hours to clean the
system hydraulic circuit (presence of solid contaminants).
-
Take another reading.
Compare this value to the initial value.
If the pressure drop has decreased, this indicates that the screen
filter must be removed and cleaned, as the hydraulic circuit
contains solid particles. In this case close the shut-off valves at
the water inlet and outlet and remove the screen filter after
emptying the hydraulic section of the unit.
Purge the air from the circuit.
Renew, if necessary, to ensure that the filter is not contaminated.
Water flow control procedure
-
When the circuit is cleaned, read the pressures at the
differential pressure gauge (BPHE leaving water pressure -
BPHE entering water pressure), to find out the pressure drop
for the plate heat exchanger and the internal piping.
-
Compare the value obtained with the theoretical selection
value.
-
If the pressure drop measured is higher than the value
specified this means that the unit flow rate (and thus system
flow rate) is too high. The pump supplies an excessive flow
rate based on the global pressure drop of the application. In
this case close the control valve or reduce the pump speed.
Read the new pressure difference.
-
Proceed by successively closing the control valve or reducing
the pump speed until you obtain the specific pressure drop
that corresponds to the nominal flow rate at the required unit
operating point.
-
Verify the minimum speed pump setting(when unit capacity
is 0%) is compatible with the flow switch protection (no flow
switch alarm for minimum speed).
NOTE: If the system has an excessive pressure drop in
relation to the available static pressure provided by the
system pump the nominal water flow rate cannot be obtained
(the resulting flow rate is lower) and the temperature
difference between the condenser entering and leaving
water will increase.
To reduce the pressure drops of the hydraulic system, it is
necessary:
-
to reduce the individual pressure drops as much as possible
(bends, level changes, accessories, etc.).
-
to use a correctly sized piping diameter.
-
to avoid hydraulic system extensions, wherever possible.
Example: TD 100 at Eurovent conditions of 1.76 l/s
Water flow rate, l/s
Pressure drop, kPa
2
1
3
4
5
B
A
0,5
1
1,5
2
2,5
3
3,5
4
0
4
8
12
16
20
Legend
B
‘BPHE pressure drop/flow rate’’ curve
C
With the valve open or with the maximum pump speed, the pressure drop read
(18 kPa) gives point A on the curve.
A Operating point reached with the valve open / maximum pump speed.
D
The flow rate achieved is 3.4 l/s: this is too high, and the valve must be closed
or the pump speed decreased.
E
With valve is partially closed or speed decreased, the pressure drop read (6
kPa) gives point B on the curve.
B Operating point reached with the valve partially closed / pump speed reduced.
F
The flow rate achieved is 1.76 l/s: this is the required flow rate and the settings
are adequate.
EN-27 AQUACIAT
CALÉO™
TD