8.4  E-mail notifications

The control system provides the option to define one or two 
recipients who receive e-mail notifications each time the new 
alarm occurs or all existing alarms have been reset. 

IMPORTANT: E-mail notifications can be set only by 

service technicians.

Connect Touch control system has many fault tracing aid 
functions, protecting the unit against risks that could result in 
the failure of the unit.

8.1  Control diagnostics

The user interface enables the quick display of the unit status:  

The 

blinking bell 

icon indicates that there is an 

alarm, but the 

unit is still running

.

The 

highlighted bell

 icon indicates that the

 unit 

is shut down 

due to a detected fault.

The local interface – Connect Touch – gives the user quick 
access to monitor all unit operating conditions. If an operating 
fault is detected, the alarm is triggered. 

All information regarding the existing alarms (current and past 

alarms) can be found in the Alarms menu.

Alarms menu

Access

Viewing alarm information

Date

Hour Code

Description

Current 

Alarms

Basic

+

+

+

Alarm 

History

Basic

+

+

+

Reset 

Alarms

User

+

8.2  Displaying current alarms

The Current alarms menu may display up to 10 current alarms.

To access the list of currently active alarms

1. Press the 

Alarm

 button in the upper-right part of the screen.

2. Select 

Current Alarms.

3. The list of active alarms will be displayed.

8.3  Resetting alarms

The alarm can be reset either automatically by the control or 
manually through the touch panel display or the web interface 

(in the Reset Alarms menu). See also section 8.5.

• 

The Reset alarms menu displays up to 5 alarm codes 

which are currently active on the unit.

•  Alarms can be reset without stopping the machine.
•  Only logged-in users can reset the alarms on the unit.

To reset the alarm manually

1. Press the 

Alarm

 button in the upper-right part of the screen.

2. Select 

Reset Alarms

.

3. Set “Alarm Reset” to Yes.

IMPORTANT: Not all alarms can be reset by the user. 

Some alarms are reset automatically when operating 

conditions return to normal.

CAUTION: In the event of a power supply interrupt, the unit 

restarts automatically without the need for an external 

command. However, any faults active when the supply is 

interrupted are saved and may in certain cases prevent 

a circuit or a unit from restarting.

8 - DIAGNOSTICS

 

 

EN - 25

 AQUACIAT

CALEO

Summary of Contents for AQUACIAT CALEO CONNECT TOUCH

Page 1: ...Instruction manual AQUACIAT CALEO 14 300 02 2018 10199 CONNECT TOUCH...

Page 2: ...he user interface provided in this manual include text in English After changing the language of the system all labels will be in the language selected by the user Please read all instructions prior t...

Page 3: ...ouch buttons 5 4 4 Menu structure 6 5 SETTING UP CONNECT TOUCH CONTROL 7 5 1 General description 7 5 2 Welcome screen 7 5 3 Synoptic screen 7 5 4 Unit start stop 7 5 5 Display settings 8 5 6 Main menu...

Page 4: ...power source RISK OF BURNS Electrical currents may cause components to get hot Handle the power cable electrical cables and conduits terminal box covers and motor frames with great care 2 1 Control sy...

Page 5: ...d to monitor the water pressure The pump is protected against cavitation low pump entering pressure 3 5 Temperature sensors Temperature sensors constantly measure the temperature of various components...

Page 6: ...sed to control the pump and unit operation open pump continues to run closed pump is stopped unit is not allowed to start DHW Tank Request Switch SIOB DI 06 63 64 Used to command the domestic hot wate...

Page 7: ...ernet connector 3 Modbus RS485 connector 4 Internal bus RS485 5 Power supply connector 24 VAC This RS 485 bus can be used as a second internal bus for the connection of gateway If it is the case then...

Page 8: ...Configuration User Configuration Pump Configuration Date Time 0 10V Pump Config Heat Cool Config Control Identification Schedule Configuration menu Main menu ModbusRTU Config ModbusTCP IP Config Netwo...

Page 9: ...ng the table content ACCESS DENIED Equipment controller denies access to one of the tables LIMIT EXCEEDED The value entered exceeds the parameter limit Save changes Modifications have been made The ex...

Page 10: ...tem allows users to add new languages to the control To learn more about language customization please contact your local service representative 5 5 2 System of measurement The control offers the poss...

Page 11: ...modifiable parameters such as pump configuration schedule menu etc The Configuration menu is password protected To access the Configuration menu press the Main menu button located in the upper left pa...

Page 12: ...HEDULE 3 Go to OCCPC01S 4 Select appropriate check boxes to set the unit occupancy on specific days 5 Define the time of occupancy 6 When the time schedule is set the selected period will be presented...

Page 13: ...the unit cannot be started stopped via the web interface All other operations including monitoring unit parameters or unit configuration can be performed via the web browser interface 5 10 2 Web brow...

Page 14: ...t selection 5 0 Auto 1 Spt1 2 Spt2 0 Auto schedule control 1 Heating setpoint 1 2 Heating setpoint 2 6 SP_OCC no yes Setpoint Occupied Setpoint occupancy status 7 CHIL_S_S disable enable Net Cmd Start...

Page 15: ...kPa Eco Suction Pressure Economizer suction pressure 4 5 INTERNAL HYDRONIC MODULE Internal hydronic module 6 W_P_IN kPa Inlet Water Pressure Inlet water pressure Displayed in French by default Setpoi...

Page 16: ...utput 17 ALARM off on Alarm Relay Status Alarm relay status 18 RUNNING off on Running Relay Status Running relay status 19 DHW_3WV off on DHW 3 Way Water Valve DHW 3 way water valve Displayed in Frenc...

Page 17: ...splayed in French by default Domestic Hot Water Menu DHW_STAT No Name Status Default Unit Displayed text Description 1 dhw_mode 0 to 2 Mode Mode 2 0 SHC 1 DHW 2 AntiLeg 0 Space Heating Control SHC 1 D...

Page 18: ...de additional features some tables may contain parameters that cannot be configured for a given unit General Config Menu GENCONF No Name Status Default Unit Displayed text Description 1 ramp_sel no ye...

Page 19: ...set Value OAT max reset value 3 dt_hr_no 0 to 14 0 K Delta T No Reset Value Delta T no reset value 4 dt_hr_fu 0 to 14 0 K Delta T Full Reset Value Delta T max reset value 5 I_hr_no 0 to 20 0 mA Curren...

Page 20: ...tware version 4 xx chars MAC address Serial Number Serial number MAC address Displayed in French by default 0 10V Pump Config Menu FLOWCONF No Name Status Default Unit Displayed text Description 1 log...

Page 21: ...Parity High 4 Force Parity High 17 stop_bit 0 to 1 0 Stop bit Stop bit 18 0 One Stop Bit 0 One Stop Bit 19 1 two Stop Bits 1 Two Stop Bits 20 real_typ 0 to 1 1 Real type management Real type managemen...

Page 22: ...y can never exceed the limit setpoint activated by these contacts The limit setpoints can be modified in the SETPOINT menu By setting DEM_LIM when the unit is in Network mode By lag limit set by the m...

Page 23: ...d through the LEN drive The status of the internal pump is displayed in the Pump Status menu under Drive pump status External Pump Output PUMP_EXT Pump Status menu and External Pump Output PUMP_EXT Ou...

Page 24: ...trol point is modified so that the machine capacity required is adjusted to be as close as possible to the demand The reset source can be provided by one of the following Outdoor air temperature that...

Page 25: ...ng mode if at least one of the following conditions applies The volt free tank request contact is open The maximum operating time for the DHW mode has elapsed Time schedule 3 is in an unoccupied perio...

Page 26: ...eating stage will not be used even if the heating demand cannot be satisfied This electric heating backup option can be enabled by setting 1 Elec Stage For Backup ehs_back to yes in the Heat Cool Conf...

Page 27: ...ory Basic Reset Alarms User 8 2 Displaying current alarms The Current alarms menu may display up to 10 current alarms To access the list of currently active alarms 1 Press the Alarm button in the uppe...

Page 28: ...e 15 4901 Loss of communication with SIOB Board Number A Bus installation fault communication error Unit shuts down Automatic if communication is re established 16 4601 Loss of communication with AUX1...

Page 29: ...company Maintenance date passed No action alert Automatic if the new maintenance date is set 37 8000 Initial Factory Configuration Required No factory configuration Unit cannot be started Automatic if...

Page 30: ...ed increase Contact Manufacturer Agency 38 over current during product speed decrease Contact Manufacturer Agency 39 over current during product speed hold Contact Manufacturer Agency 41 drive type er...

Page 31: ...erious damage can occur to your equipment TheManufacturerprovidesawiderangeofservicecontractswhich embrace the assistance of highly qualified HVAC engineering professionals ready to help if needed The...

Page 32: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Reviews: