5  -  SETTING UP CONNECT TOUCH CONTROL 

Unit start/stop screen (operating modes):

Local On

Local On: The unit is in the local control mode and 

allowed to start.

Local 

Schedule

Local Schedule: The unit is in the local control mode and 

allowed to start if the period is occupied.

Network

Network: The unit is controlled by network commands and 

allowed to start if the period is occupied.

Remote

Remote: The unit is controlled by external commands and 

allowed to start if the period is occupied.

Master

Master: The unit operates as the master in the master/slave 

assembly and allowed to start if the period is occupied.

To start the unit

1.  Press the 

Start/Stop 

button.

2.  Select the required Machine Mode.

3.  The Welcome screen will be displayed.

To stop the unit 

1.  Press the 

Start/Stop

 button.

2.  Confirm  the  unit  shutdown  by  pressing 

Confirm  Stop

 or 

cancel the unit shutdown by pressing the

 Back 

button. 

 

The bell located in the upper-right part of the screen 
lights when any fault is detected.

5.5  Display settings

The User Login screen allows the user to do any of the following:

• 

Select the language of the controller.

•  Change the system of measurement (imperial or metric). 
•  Gain access to more control options.

To access the User Login screen, press the

 Login 

button 

 

in the upper-right corner of the Synoptic screen.

1. Cursor indicating the selected language

2. Logged-in button

3. Logged-off button

4. Password dialog box

5. System of measurement: Metric/Imperial

5.5.1  Display language

Display language can be modified in the User Login Screen on 

the user interface.

To change a display language

1.  Press the 

Login

 button to open User Login Screen.

2.  Select the new language of the display.
3.  Press the 

Logged-in

 button to save your changes or  

 the 

Logged-off

 button to exit the screen without making  

  modifications.

The control system allows users to add new languages to the 
control. To learn more about language customization, please 
contact your local service representative.

5.5.2  System of measurement

The control offers the possibility of selecting the system of 
measurement displayed on the user interface (metric / imperial).

To change a system of measurement

1.  Press the 

Login

 button to open User Login Screen.

2.  Select the system of measurement (metric or imperial).
3.  Press the 

Logged-in

 button to save your changes or  

 the 

Logged-off

 button to exit the screen without making  

  modifications.

5.5.3  User login

Only logged-in users can access configurable unit parameters. 

By default, user password is “11”. 

To log in as user

1.  Press the Login button to open User Login Screen. 
2.  Press the Password box. A dialog box appears.
3.  Provide the password (11) and press 

OK

4.  The User Login screen appears.

5.  Press  the 

Logged-in

 button to save your changes or 

the

 Logged-off 

button  to  exit  the  screen  without  making 

modifications.

NOTE: You may also leave the User Login screen by 

pressing the Back button. Your changes will be saved.

Security access settings

•  User-level security ensures that only authorised users 

are allowed to modify critical unit parameters. 

•  Only logged-in users are allowed to access the 

Configuration menu.

•  It is strongly recommended to change the default 

password of the user interface to exclude the possibility 
of changing any parameters by an unqualified person.

• 

Only people qualified to manage the unit should be 

familiarized with the password.

5.5.4  Password change

User password can be modified in the User Configuration menu.

To change your password

1.  Go to the Main Menu. 
2.  Navigate to the Configuration menu (logged-in users only)  

  and select 

User Configuration

 (USERCONF).

3.  Select the User Password box and provide the new password.
4.  Press 

OK

. The User Configuration screen appears.

5.  Press the 

Save

 button to save your changes or the

 Cancel  

 

button to exit the screen without making modifications.

1

2

3

4

5

 

AQUACIAT

CALEO

 

 EN - 8

 

Summary of Contents for AQUACIAT CALEO CONNECT TOUCH

Page 1: ...Instruction manual AQUACIAT CALEO 14 300 02 2018 10199 CONNECT TOUCH...

Page 2: ...he user interface provided in this manual include text in English After changing the language of the system all labels will be in the language selected by the user Please read all instructions prior t...

Page 3: ...ouch buttons 5 4 4 Menu structure 6 5 SETTING UP CONNECT TOUCH CONTROL 7 5 1 General description 7 5 2 Welcome screen 7 5 3 Synoptic screen 7 5 4 Unit start stop 7 5 5 Display settings 8 5 6 Main menu...

Page 4: ...power source RISK OF BURNS Electrical currents may cause components to get hot Handle the power cable electrical cables and conduits terminal box covers and motor frames with great care 2 1 Control sy...

Page 5: ...d to monitor the water pressure The pump is protected against cavitation low pump entering pressure 3 5 Temperature sensors Temperature sensors constantly measure the temperature of various components...

Page 6: ...sed to control the pump and unit operation open pump continues to run closed pump is stopped unit is not allowed to start DHW Tank Request Switch SIOB DI 06 63 64 Used to command the domestic hot wate...

Page 7: ...ernet connector 3 Modbus RS485 connector 4 Internal bus RS485 5 Power supply connector 24 VAC This RS 485 bus can be used as a second internal bus for the connection of gateway If it is the case then...

Page 8: ...Configuration User Configuration Pump Configuration Date Time 0 10V Pump Config Heat Cool Config Control Identification Schedule Configuration menu Main menu ModbusRTU Config ModbusTCP IP Config Netwo...

Page 9: ...ng the table content ACCESS DENIED Equipment controller denies access to one of the tables LIMIT EXCEEDED The value entered exceeds the parameter limit Save changes Modifications have been made The ex...

Page 10: ...tem allows users to add new languages to the control To learn more about language customization please contact your local service representative 5 5 2 System of measurement The control offers the poss...

Page 11: ...modifiable parameters such as pump configuration schedule menu etc The Configuration menu is password protected To access the Configuration menu press the Main menu button located in the upper left pa...

Page 12: ...HEDULE 3 Go to OCCPC01S 4 Select appropriate check boxes to set the unit occupancy on specific days 5 Define the time of occupancy 6 When the time schedule is set the selected period will be presented...

Page 13: ...the unit cannot be started stopped via the web interface All other operations including monitoring unit parameters or unit configuration can be performed via the web browser interface 5 10 2 Web brow...

Page 14: ...t selection 5 0 Auto 1 Spt1 2 Spt2 0 Auto schedule control 1 Heating setpoint 1 2 Heating setpoint 2 6 SP_OCC no yes Setpoint Occupied Setpoint occupancy status 7 CHIL_S_S disable enable Net Cmd Start...

Page 15: ...kPa Eco Suction Pressure Economizer suction pressure 4 5 INTERNAL HYDRONIC MODULE Internal hydronic module 6 W_P_IN kPa Inlet Water Pressure Inlet water pressure Displayed in French by default Setpoi...

Page 16: ...utput 17 ALARM off on Alarm Relay Status Alarm relay status 18 RUNNING off on Running Relay Status Running relay status 19 DHW_3WV off on DHW 3 Way Water Valve DHW 3 way water valve Displayed in Frenc...

Page 17: ...splayed in French by default Domestic Hot Water Menu DHW_STAT No Name Status Default Unit Displayed text Description 1 dhw_mode 0 to 2 Mode Mode 2 0 SHC 1 DHW 2 AntiLeg 0 Space Heating Control SHC 1 D...

Page 18: ...de additional features some tables may contain parameters that cannot be configured for a given unit General Config Menu GENCONF No Name Status Default Unit Displayed text Description 1 ramp_sel no ye...

Page 19: ...set Value OAT max reset value 3 dt_hr_no 0 to 14 0 K Delta T No Reset Value Delta T no reset value 4 dt_hr_fu 0 to 14 0 K Delta T Full Reset Value Delta T max reset value 5 I_hr_no 0 to 20 0 mA Curren...

Page 20: ...tware version 4 xx chars MAC address Serial Number Serial number MAC address Displayed in French by default 0 10V Pump Config Menu FLOWCONF No Name Status Default Unit Displayed text Description 1 log...

Page 21: ...Parity High 4 Force Parity High 17 stop_bit 0 to 1 0 Stop bit Stop bit 18 0 One Stop Bit 0 One Stop Bit 19 1 two Stop Bits 1 Two Stop Bits 20 real_typ 0 to 1 1 Real type management Real type managemen...

Page 22: ...y can never exceed the limit setpoint activated by these contacts The limit setpoints can be modified in the SETPOINT menu By setting DEM_LIM when the unit is in Network mode By lag limit set by the m...

Page 23: ...d through the LEN drive The status of the internal pump is displayed in the Pump Status menu under Drive pump status External Pump Output PUMP_EXT Pump Status menu and External Pump Output PUMP_EXT Ou...

Page 24: ...trol point is modified so that the machine capacity required is adjusted to be as close as possible to the demand The reset source can be provided by one of the following Outdoor air temperature that...

Page 25: ...ng mode if at least one of the following conditions applies The volt free tank request contact is open The maximum operating time for the DHW mode has elapsed Time schedule 3 is in an unoccupied perio...

Page 26: ...eating stage will not be used even if the heating demand cannot be satisfied This electric heating backup option can be enabled by setting 1 Elec Stage For Backup ehs_back to yes in the Heat Cool Conf...

Page 27: ...ory Basic Reset Alarms User 8 2 Displaying current alarms The Current alarms menu may display up to 10 current alarms To access the list of currently active alarms 1 Press the Alarm button in the uppe...

Page 28: ...e 15 4901 Loss of communication with SIOB Board Number A Bus installation fault communication error Unit shuts down Automatic if communication is re established 16 4601 Loss of communication with AUX1...

Page 29: ...company Maintenance date passed No action alert Automatic if the new maintenance date is set 37 8000 Initial Factory Configuration Required No factory configuration Unit cannot be started Automatic if...

Page 30: ...ed increase Contact Manufacturer Agency 38 over current during product speed decrease Contact Manufacturer Agency 39 over current during product speed hold Contact Manufacturer Agency 41 drive type er...

Page 31: ...erious damage can occur to your equipment TheManufacturerprovidesawiderangeofservicecontractswhich embrace the assistance of highly qualified HVAC engineering professionals ready to help if needed The...

Page 32: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Reviews: