Date/Time Menu – DATETIME
No. Name
Status
Default Unit Displayed text *
Description
Date (DD/MM/YYYY)
1
d_of_m
1 to 31
-
-
Day of month
Day of the month
2
month
1 to 12
-
-
Month of year
Month
3
year
20nn
-
-
Year
Year
4
dow
Monday-Sunday -
-
Day of Week
Day of the week
Time (HH:MM)
5
hour
0 to 24
-
h
Hour
Hour
6
minute
0 to 59
min
Minute
Minutes
Daylight Saving Time
7
dlig_on
no/yes
-
-
Daylight sav. time on
Daylight saving time active
8
dlig_off
no/yes
-
-
Daylight sav. time off
Daylight saving time inactive
9
tom_hol
no/yes
-
-
Tomorrow is a holiday
The following day is a holiday
10
tod_hol
no/yes
-
-
Today is a holiday
The present day is a holiday
*Displayed in French by default.
Control Identification Menu – CTRL_ID
No. Name Status
Default
Unit Displayed text *
Description
1
-
"xx chars" TD
-
Device Description
Device description
2
-
"xx chars"
-
Location Description
Location description: The number corresponds to the country
3
-
"xx chars" ECG-SR-20RF1-xxx
-
Software Part Number
Software version
4
-
"xx chars" MAC address
-
Serial Number
Serial number (MAC address)
*Displayed in French by default.
0-10V Pump Config Menu – FLOWCONF
No. Name
Status
Default
Unit Displayed text *
Description
1
logictyp
0 to 2
0
-
Logic: 0=No,1=STEP,2=PID
Logic type:
0 = No 0-10V external pump
1 = 0-10V External Pump controlled by Step Logic
2 = 0-10V External Pump controlled by PID Logic
2
minspeed
0 to 45
10
%
Minimum Pump Speed
Minimum pump speed
3
maxspeed
55 to 100
100
%
Maximum Pump Speed
Maximum pump speed
4
step
1 to 20
5
-
Pump Speed Step
Pump speed step
5
dt_stp
2 to 20
5
K
Water Delta T Setpoint
Water delta T setpoint
6
deadband
0.5 to 2
1
K
Deadband (for Step ctrl)
Deadband for step control
7
dt_kp
-10 to 10
-2
-
PID Control Prop. Gain
PID control proportional gain
8
dt_ki
-10 to 10
-0.2
-
PID Control Integ. Gain
PID control integrative gain
9
dt_kd
-10 to 10
0
-
PID Control Deriv. Gain
PID control derivative gain
10
timer
1 to 60
10
sec
Reschedule Timer
Reschedule timer (delay before the new calculation is made – used for both
Step and PID logic control)