background image

dIXEL

 

Installing and Operating Instructions 

1592027320

 

 

1592027320 XW20LS RTC GB r1.0 10.07.2008.doc 

XW20LS 

4/5 

3.

 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Controller memory, 

the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then 

on if you want to restart the download again or remove the “

Hot key

” to abort the operation. 

14.

 

ALARM SIGNALS 

Message  

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. “Con” and “COF” 

“P2” 

Evaporator probe  failure 

Defrost end is timed 

“P3” 

Third probe  failure 

Outputs unchanged 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

"HA2" 

Condenser high temperature 

It depends on the “Ac2” parameter 

"LA2" 

Condenser low temperature 

It depends on the “bLL” parameter 

“dA” 

Door open 

Compressor and fans restarts  

“EA”  

External alarm 

Output unchanged. 

“CA”  

Serious external alarm (i1F=bAL)  All outputs OFF. 

“CA” 

Pressure switch alarm (i1F=PAL)  All outputs OFF 

“rtc” 

Real time clock alarm 

Alarm output ON; Other outputs unchanged; 
Defrosts according to par. “IdF” Set real time clock 
has to be set 

rtF 

Real time clock board failure 

Alarm output ON; Other outputs unchanged; 
Defrosts according to par. “IdF” Contact the 
service 

14.1

 

SILENCING BUZZER / ALARM RELAY OUTPUT 

If “

tbA = y

”, the buzzer and the relay are is silenced by pressing any key.  

If “

tbA 

n

”, only the buzzer is silenced while the alarm relay is on until the alarm condition recovers. 

14.2

 

ALARM RECOVERY  

Probe alarms 

P1

”, “

P2”,

  “

P3

” start some seconds after the fault in the related probe; they 

automatically stop some seconds after the probe restarts normal operation. Check connections 
before replacing the probe. 
Temperature alarms “

HA

”, “

LA

” “

HA2

” and “

LA2

” automatically stop as soon as the temperature 

returns to normal values. 
Alarms 

“EA”

 and 

“CA” 

(with i1F=bAL)

 

recover as soon as the digital input is disabled. 

Alarm “

CA”

 (with i1F=PAL) recovers only by 

switching off and on

 the instrument. 

14.3

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode

: none parameter is present in Pr1 

On the display

 or in dP2, dP3, dP4: the selected probe is nor enabled 

15.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: 

facia 38x185 mm; depth 48mm 

Mounting :

 panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm. 

 

Distance between the holes 165mm 

Protection: 

IP20; 

Frontal protection:

 IP65 with frontal gasket mod RG-L. (optional) 

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm Faston 

Power supply: 

230Vac or. 110Vac or 24Vac 

±

 10%; 

Power absorption: 

5VA max.

 

Display

: 3 digits, red LED, 14,2 mm high; 

Inputs

: Up to 3 NTC or PTC probes.

 

Digital input

: 1 free voltage 

Relay outputs: 

Total current on loads MAX. 20A

 

compressor:

 relay SPST 20(8) A, 250Vac  

light: 

relay SPST 7 A, 250Vac  

Other output :

 buzzer (optional) 

Serial output :

 TTL standard; 

Communication protocol:

 Modbus - RTU

 

Data storing

: on the non-volatile memory (EEPROM). 

Internal clock back-up:

 24 hours (only for model with RTC) 

Kind of action: 

1B; 

Pollution grade: 

2;

Software class: 

A.;  

Rated impulsive voltage

: 2500V; 

Over voltage Category

: II

 

Operating temperature: 

0÷60 °C; 

Storage temperature: 

-30÷85 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-40÷230°F);  

PTC probe: 

-50÷150°C (-58÷302°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable); 

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit 

16.

 

CONNECTIONS 

16.1

 

XW20LS – DRY CONTACTS 

 

 

 
Supply: 120Vac or 24Vac: 

connect to terminals 7-8

 

The X-REP

 

output

 is optional 

16.2

 

XW20LS – DIRECT CONNECTIONS OF LOAD 

 

 
Supply: 120Vac or 24Vac: 

connect to terminals 5-6

 

The X-REP

 

output

 is optional 

 

17.

 

DEFAULT SETTING VALUES 

Label Name 

Range 

°C/°F 

Level 

Set 

Set point 

LS÷US 

3.0 - 

rtc* 

Real time clock menu 

Pr1 

Hy 

Differential 

0,1

÷

25.5°C/ 1

÷

 255°F 

2.0 Pr1 

LS 

Minimum set point 

-50°C

÷

SET/-58°F

÷

SET 

-50.0 Pr2 

US 

Maximum set point 

SET

÷

110°C/ SET 

÷

 230°F 

110 Pr2 

Ot 

Thermostat probe calibration 

-12

÷

12°C /-120

÷

120°F 

0.0 Pr1 

P2P 

Evaporator probe presence 

n=not present; Y=pres. 

Pr1 

OE 

Evaporator probe calibration 

-12

÷

12°C /-120

÷

120°F 

0.0 Pr2 

P3P 

Third probe presence 

n=not present; Y=pres. 

Pr2 

O3 

Third probe calibration 

-12

÷

12°C /-120

÷

120°F 

0 Pr2 

OdS 

Outputs delay at start up 

0÷255 min 

Pr2 

AC 

Anti-short cycle delay 

÷

 50 min 

1 Pr1 

rtr 

P1-P2 percentage for regulation 

 0 ÷ 100 (100=P1 , 0=P2) 

100 

Pr2 

CCt 

Continuous cycle duration 

0.0÷24.0h 

0.0 

Pr2 

CCS 

Set point for continuous cycle 

 (-55.0÷150,0°C) (-67÷302°F) 

3.0 

Pr2 

COn 

Compressor ON time with faulty probe 

÷

 255 min 

15 Pr2 

COF 

Compressor OFF time with faulty probe 

÷

 255 min 

30 Pr2 

CH 

Kind of action 

cL÷Ht 

cL Pr1 

CF 

Temperature measurement unit 

°C 

÷

 °F 

°C Pr2 

rES 

Resolution in=integer; 

dE= 

dec.point 

dE 

Pr1 

Lod 

Probe displayed 

P1;P2 

P1 

Pr2 

rEd

X-REP display 

P1 – P2 – P3 – P4 – SEt – dtr 

P1 

Pr2 

dLy 

Display temperature delay   

0 ÷ 20.0 min  (10 sec.)  

0.0 

Pr2 

dtr 

P1-P2 percentage for display 

 1 ÷ 99 

50 

Pr2 

EdF* 

Kind of interval for defrost 

rtc ÷in 

in 

Pr2 

dFP 

Probe selection for defrost termination 

nP; P1; P2; P3; P4 

nP 

Pr2 

dtE 

Defrost termination temperature 

-50 

÷

 50 °C 

3 Pr1 

IdF 

Interval between defrost cycles 

÷

 120 ore 

8 Pr1 

MdF 

(Maximum) length for defrost 

÷

 255 min 

20 Pr1 

dFd 

Displaying during defrost 

rt, it, SEt, DEF 

it 

Pr2 

dAd 

MAX display delay after defrost 

0 ÷ 255 min 

30 

Pr2 

ALP 

Alarm probe selection  

nP; P1; P2; P3; P4 

P1 

Pr2 

ALc 

Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

Ab Pr2 

ALU 

MAXIMUM temperature alarm 

Set

÷

110.0°C; Set÷230°F 

110,0 Pr1 

ALL 

Minimum temperature alarm 

-50.0°C

÷

Set/ -58°F

÷

Set 

-50,0 Pr1 

AFH 

Differential for temperat. alarm recovery 

(0,1°C÷25,5°C) (1°F÷45°F) 

2,0 

Pr2 

ALd 

Temperature alarm delay 

÷

 255 min 

15 Pr2 

dAO 

Delay of temperature alarm at start up 

÷

 23h e 50’ 

1,3 Pr2 

AP2 

Probe for temperat. alarm of condenser 

nP; P1; P2; P3; P4 

nP 

Pr2 

AL2 

Condenser for low temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

-40 

Pr2 

AU2 

Condenser for high temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

110 

Pr2 

AH2 

Differ. for condenser temp. alar. recovery 

[0,1°C ÷ 25,5°C]  [1°F ÷ 45°F] 

Pr2 

Ad2 

Condenser temperature alarm delay  

 0 ÷ 254 (min.) , 255=nU 

15 

Pr2 

dA2 

Delay of cond. temper. alarm at start up 

0.0 ÷ 23h  50’ 

1,3 

Pr2 

bLL 

Compr. off for condenser low temper. alarm 

n(0) - Y(1) 

Pr2 

AC2 

Compr. off for condenser high temper alarm 

n(0) - Y(1) 

Pr2 

i1P 

Digital input polarity (13-14) 

oP=opening;CL=closing 

cL 

Pr1 

i1F 

Digital input 1 configuration (13-14) 

EAL, bAL, PAL, dor; dEF; Htr, AUS

dor 

Pr1 

did 

Digital input alarm delay (13-14) 

0÷255min 

15 

Pr1 

Nps 

Number of activation of pressure switch 

0 ÷15  

15 

Pr2 

odc 

Compress status when open door 

no; Fan; CPr; F_C  

F-c 

Pr2 

rrd 

Regulation restart with door open alarm 

n – Y 

Pr2 

HES 

Differential for Energy Saving 

 (-30°C÷30°C) (-54°F÷54°F) 

Pr2 

Hur* 

Current hour 

0 ÷ 23 

rtc 

Min* 

Current minute 

0 ÷ 59 

rtc 

dAY* 

Current day 

Sun ÷ SAt 

rtc 

Hd1* 

First weekly holiday 

Sun÷ SAt – nu 

nu 

rtc 

Hd2* 

Second weekly holiday 

Sun÷ SAt – nu 

nu 

rtc 

ILE* 

Energy Saving cycle start during workdays 

0 ÷ 23h 50 min. 

rtc 

dLE* 

Energy Saving cycle length during workdays 

0 ÷ 24h 00 min. 

rtc 

ISE* 

Energy Saving cycle start on holidays 

0 ÷ 23h 50 min. 

rtc 

dSE* 

Energy Saving cycle length on holidays 

0 ÷ 24h 00 min. 

rtc 

Ld1* 

1

st

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

6.0 

rtc 

Ld2* 

2

nd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

13.0 

rtc 

Ld3* 

3

rd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

21.0 

rtc 

Ld4* 

4

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

0.0 

rtc 

Ld5* 

5

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

0.0 

rtc 

Ld6* 

6

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

0.0 

rtc 

Summary of Contents for 6040 Series

Page 1: ...Refrigerated Pastry Showcase 6040 SERIES Maintenance And Use Manual CIAMspa 06081 Petrignano d Assisi PG Italy tel 075 80161 Fax 075 8016215 http www ciamgroup it e mail info ciamgroup it...

Page 2: ...or refrigerators freezers and ice machines 1 4 RESPONSIBILITY Ciam declines any responsibility relevant to damages on persons animals and or products in case of No respect of in force norms Installati...

Page 3: ...ong stock have not to be ascribed to the manufacturer 3 4 DISPLAY CABINET POSITION The refrigerated display cabinet needs particular environmental conditions in order to offer the right performance so...

Page 4: ...et in order to make easy any type of check and maintenance operations When the condensing units are external will be necessary a frame holder that has to be fixed in a proper way and eventually added...

Page 5: ...a wet cloth weekly Additional defrost Under particular conditions of temperature and humidity the frost that normally forms on the evaporator and fans might increase in volume so leading to a faulty f...

Page 6: ...G ELEMENT SUCTION AIR GLASS HEATING ELEMENT OUTLET AIR HEATING ELEMENT REAR GLASS HEATING ELEMENT INTERNAL GLASS HEATING ELEMENT FRONT GLASS UPPER FRAME HEATING ELEMENT FRONT GLASS LATERAL LOWER FRAME...

Page 7: ......

Page 8: ......

Page 9: ...s length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTROL OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C_n fans will switch ON...

Page 10: ...THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA Each parameter present in the HIDDEN MENU can be removed or put into THE FIRST LEVEL user level by pressing SET n In HIDDEN MENU when a parameter is p...

Page 11: ...ture alarm delay 0 255 min time interval between the detection of an alarm condition and alarm signalling dAO Exclusion of temperature alarm at start up from 0 0 min to 23 5h time interval between the...

Page 12: ...TORING SYSTEMS The TTL serial line available through the HOT KEY connector allows by means of the external TTL RS485 converter XJ485 CX to connect the instrument to a monitoring system ModBUS RTU comp...

Page 13: ...ous cycle duration 0 0 24 0h 0 0 Pr2 CCS Set point for continuous cycle 55 0 150 0 C 67 302 F 5 Pr2 COn Compressor ON time with faulty probe 0 255 min 15 Pr2 COF Compressor OFF time with faulty probe...

Page 14: ...50 min nu 13 0 rtc Sd3 3rd holiday defrost start 0 23h 50 min nu 21 0 rtc Sd4 4th holiday defrost start 0 23h 50 min nu 0 0 rtc Sd5 5th holiday defrost start 0 23h 50 min nu 0 0 rtc Sd6 6th holiday de...

Page 15: ...standard way for controller without RTC with EdF rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld6 on workdays and in Sd1 Sd6 in holidays Other parameters are u...

Page 16: ...visualization rEd X REP display optional P1 P2 P3 P4 SET dtr it selects which probe is displayed by X REP P1 Thermostat probe P2 Evaporator probe P3 Third probe only for model with this option enabled...

Page 17: ...will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 8 6 INVERSION OF THE KIND OF ACTION HEATING COOLING i1F Htr This function all...

Page 18: ...XW20LS DIRECT CONNECTIONS OF LOAD Supply 120Vac or 24Vac connect to terminals 5 6 The X REP output is optional 17 DEFAULT SETTING VALUES Label Name Range C F Level Set Set point LS US 3 0 rtc Real tim...

Page 19: ...start 0 23h 50 min nu 0 0 rtc Sd6 6th holiday defrost start 0 23h 50 min nu 0 0 rtc Adr Serial address 1 247 1 Pr2 PbC Kind of probe Ptc ntc ntc Pr2 onF on off key enabling nu oFF ES oFF Pr2 dP1 Room...

Reviews: