CIAM 6040 Series Maintenance And Use Manual Download Page 11

dIXEL

 

Installing and Operating Instructions 

1592027050

 

 

1592027050 XW60L RTC GB r1.0 27.06.2008.doc 

XW60L 

3/6 

Lod Instrument display

: (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by the 

instrument: 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe(only for model 

with this option enabled); 

P4

 = Fourth probe,

 SET

 = set point;  

dtr

 = percentage of 

visualization. 

rEd  X- REP display (

optional

)

: (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by 

X- REP: 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe(only for model with 

this option enabled); 

P4

 = Fourth probe,

 SET

 = set point;  

dtr

 = percentage of visualization. 

dLy Display delay: 

(0 ÷20.0m; resul. 10s) when the temperature increases, the display is updated 

of 1 °C/1°F after this time. 

dtr  Percentage of the second and first probe for visualization when Lod = dtr (0÷100; 100 = 

P1, 0 = P2 ): if Lod = dtr 

it allows to set the visualization according to the percentage of the 

first and second probe, as for the following formula (dtr(P1-P2)/100 + P2). 

DEFROST 
EdF  Defrost mode (only for controller with RTC):

    

 rtc 

Real Time Clock mode

. Defrost time follows 

Ld1÷Ld6

 parameters on workdays and 

Sd1÷Sd6

 on holidays. 

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

tdF   Defrost type

: EL = electrical heater; in = hot gas 

dFP Probe selection for defrost termination: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

dtE  Defrost termination temperature

: (-50÷50 °C/  

-58÷122°F) (Enabled only when EdF=Pb) sets the temperature measured by the evaporator 
probe, which causes the end of defrost. 

IdF  Interval between defrost cycles

: (0÷120h) Determines the time interval between the 

beginning of two defrost cycles. 

MdF  (Maximum) length for defrost

: (0÷255min) When 

P2P = n

, (not evaporator probe: timed 

defrost) it sets the defrost duration, when 

P2P = y

 (defrost end based on temperature) it sets 

the maximum length for defrost. 

dSd Start defrost delay

: ( 0÷99min) This is useful when different defrost start times are necessary 

to avoid overloading the plant.  

dFd  Temperature displayed during defrost

: (

rt

 = real temperature; 

it

 = temperature at defrost 

start; 

SEt

 = set point; 

dEF

 = “dEF” label) 

dAd MAX display delay after defrost

: (0÷255min). Sets the maximum time between the end of 

defrost and the restarting of the real room temperature display. 

Fdt Drip time

: (0

÷

120 min) time interval between reaching defrost termination temperature and the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water 
drops that might have formed due to defrost. 

dPo  First defrost after start-up

: (y = immediately; n = after the IdF time) 

dAF Defrost delay after continuous cycle

: (0

÷

23.5h) time interval between the end of the fast 

freezing cycle and the following defrost related to it. 

FANS 
FnC Fans operating mode

C-n

= runs with the compressor, OFF during defrost;  

o-n

 = continuous mode, OFF during defrost;  

C-Y

 = runs with the compressor, ON during defrost;  

o-Y

 = continuous mode, ON during defrost;  

Fnd Fans delay after defrost:

 (0÷255min) Interval between end of defrost and evaporator fans 

start.

 

Fct  Temperature differential avoiding short cycles of fans 

(0÷59°C; Fct=0 function disabled). If 

the difference of temperature between the evaporator and the room probes is more than the 
value of the Fct parameter, the fans are switched on.

 

FSt  Fans stop temperature

: (-50÷50°C/122°F) setting of temperature, detected by evaporator 

probe, above which fans are always OFF. 

Fon Fan ON time:

 (0÷15 min)

 with 

Fnc = C_n or C_y, (fan activated in parallel with compressor). it 

sets the evaporator fan ON cycling time when the compressor is off. With Fon =0 and FoF 

 0 

the fan are always off, with Fon=0 and FoF =0 the fan are always off.

 

FoF Fan OFF time:

 (0÷15 min)

 with 

Fnc = C_n or C_y, (fan activated in parallel with compressor). it 

sets the evaporator fan off cycling time when the compressor is off. With Fon =0 and FoF 

 0 

the fan are always off, with Fon=0 and FoF =0 the fan are always off.

 

FAP  Probe selection for fan management: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator 

probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

AUXILIARY THERMOSTAT CONFIGURATION (terms. 1-3) – OA3 = AUS 
ACH  Kind of regulation for auxiliary relay

Ht 

= heating; 

CL 

= cooling 

SAA  Set Point for auxiliary relay:

 (-50,0÷110,0°C; -58÷230°F) it defines the room temperature set 

point  to switch auxiliary relay.

 

SHy Differential for auxiliary output: 

(0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for 

auxiliary output set point.  

With ACH = cL 

AUX Cut in is SAA + SHy; . AUX Cut  out is SAA 

With ACH = Ht 

AUX Cut in is SAA - SHy; . AUX Cut out  is SAA 

ArP  Probe selection for auxiliary

: nP = no probe, the auxiliary relay is switched only by button; 

P1 

Probe 1 (Thermostat probe); 

P2 = 

Probe 2 (evaporator probe); 

P3 = 

Probe 3 (display probe); 

P4 = 

Probe 4 fourth probe. 

Sdd  Auxiliary relay off during defrost: n = 

the auxiliary relay operates during defrost. 

 y 

the auxiliary relay is switched off during defrost. 

ALARMS 
ALP  Probe selection for alarm

: nP = no probe, the temperature alarms are disabled; 

P1 = 

Probe 1 

(Thermostat probe); 

P2 = 

Probe 2 (evaporator probe); 

P3 = 

Probe 3 (display probe); 

P4 = 

Fourth probe. 

ALC  Temperature alarms configuration:

 (Ab; rE) 

 

Ab

= absolute temperature: alarm temperature is given by the ALL or ALU values.  

rE

 = 

temperature alarms are referred to the set point. Temperature alarm is enabled when the 
temperature exceeds the “SET+ALU” or “SET-ALL” values. 

ALU  MAXIMUM temperature alarm

: (SET÷110°C; SET÷230°F) when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

ALL Minimum temperature alarm

: (-50.0 ÷ SET °C; -58÷230°F when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

AFH Differential for temperature alarm/ fan recovery: 

(0,1÷25,5°C; 1÷45°F) Intervention 

differential for recovery of temperature alarm. It’s also used for the restart of the fan when the 
FSt temperature is reached  

ALd  Temperature alarm delay

: (0÷255 min) time interval between the detection of an alarm 

condition and alarm signalling. 

dAO Exclusion of temperature alarm at start-up

: (from 0.0 min to 23.5h) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling. 

CONDENSER TEMPERATURE ALARM 
AP2  Probe selection for temperature alarm of condenser: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

AL2 Low temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the 

LA2 alarm is signalled, possibly after the Ad2 delay. 

Au2 High temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the 

HA2 alarm is signalled, possibly after the Ad2 delay. 

AH2 Differential for temperature condenser alarm recovery

:

 

(0,1÷25,5°C; 1÷45°F) 

Ad2 Condenser temperature alarm delay

: (0÷255 min) time interval between the detection of the 

condenser alarm condition and alarm signalling. 

dA2 Condenser temperature alarm exclusion at start up

: (from 0.0 min to 23.5h, res. 10min) 

bLL  Compressor off with low temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

AC2 Compressor off with high temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

AUXILIARY RELAY 
tbA  Alarm relay silencing (with oA3 =ALr):  

n

= silencing disabled: alarm relay stays on till alarm condition lasts,  

=silencing enabled: alarm relay is switched OFF by pressing a key during an alarm 

oA3 Fourth relay configuration (1-3):

 

dEF, FAn: 

do not select it!.

 ALr

: alarm; 

Lig

: light;

 AuS

Auxiliary relay; 

onF

: always on with instrument on; 

db= 

neutral zone; 

cP2 = 

second 

compressor;  

dEF2: 

do not select it!;.

 HES:

. night blind

 

AoP Alarm relay polarity: 

it set if the alarm relay is open or closed when an alarm happens. 

CL

terminals 1-3 closed during an alarm; 

oP

 = terminals 1-3 open during an alarm

 

DIGITAL INPUTS 
i1P  Digital input polarity (13-14): oP: 

the digital input is activated by opening the contact; 

CL: 

the 

digital input is activated by closing the contact.

 

i1F Digital input configuration (13-14): EAL

= external alarm: “EA” message is displayed; 

bAL

serious alarm “CA” message is displayed. 

PAL

= pressure switch alarm, “CA” message is 

displayed; 

dor

= door switch function; 

dEF

= activation of a defrost cycle; 

AUS

=not enabled; 

Htr

= kind of action inversion (cooling – heating); 

FAn

=

 not set it; ES

=

 

Energy saving; 

HdF 

=

 

Holiday defrost (enable only with RTC); 

onF = 

to switch the controller off. 

did 

(0

÷

255 min) 

with

 

i1F= EAL or i1F = bAL digital input alarm delay (13-14):

 delay between the 

detection of the external alarm condition and its signalling. 

with

 

i1F= dor: door open signalling delay 

with i1F= PAL: time for pressure switch function: 

time interval to calculate the number of 

the pressure switch activation. 

i2P 2

nd

 digital input polarity (13-19): oP: 

the digital input is activated by opening the contact; 

CL: 

the digital input is activated by closing the contact.

 

i2F  2

nd

 digital input configuration (13-19): EAL

= external alarm: “EA” message is displayed; 

bAL

= serious alarm “CA” message is displayed. 

PAL

= pressure switch alarm, “CA” message is 

displayed; 

dor

= door switch function; 

dEF

= activation of a defrost cycle; 

AUS

=not enabled; 

Htr

= kind of action inversion (cooling – heating); 

FAn

=

 not set it; ES

=

 

Energy saving; 

HdF 

=

 

Holiday defrost (enable only with RTC); 

onF = 

to switch the controller off. 

d2d 

(0

÷

255 min) 

with

 

i2F= EAL or i2F= bAL 2

nd

 digital input alarm delay (13-19):

 delay between 

the detection of the external alarm condition and its signalling. 

with

 

i2F= dor: door open signalling delay 

with i2F= PAL: time for pressure switch function: 

time interval to calculate the number of 

the pressure switch activation. 

nPS Pressure switch number:

 (0 

÷

15) Number of activation of the pressure switch, during the “

did

” 

interval, before signalling the alarm event (I2F= PAL).  

If the nPS activation in the did time is reached, switch off and on the instrument to 

restart normal regulation. 

odc  Compressor and fan status when open door:

   

no

 = normal; 

Fan

 = Fan OFF; 

CPr 

Compressor OFF; 

F_C

 = Compressor and fan OFF.  

rrd  Outputs restart after doA alarm: no= 

outputs not affected by the doA alarm;  

yES = 

outputs 

restart with the doA alarm. 

HES Temperature increase during the Energy Saving cycle: 

(-30,0°C

÷

30,0°C) it sets the increasing value of the set point during the Energy Saving cycle.  

TO SET CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC) 
Hur Current 

hour 

(0 ÷ 23 h) 

Min Current 

minute

 (0 ÷ 59min) 

dAY Current 

day

 (Sun ÷ SAt) 

Hd1 First 

weekly 

holiday 

(Sun ÷ nu) Set the first day of the week which follows the holiday 

times. 

Hd2  Second weekly holiday 

(Sun ÷ nu) Set the second day of the week which follows the 

holiday times. 

N.B.   Hd1,Hd2 

can be set also as

 “nu” 

value (Not Used).

  

TO SET ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC) 
ILE 

Energy Saving cycle start during workdays

: (0 ÷ 23h 50 min.) During the Energy Saving 

cycle the set point is increased by the value in HES so that the operation set point is SET + 
HES.  

dLE 

Energy Saving cycle length during workdays

: (0 ÷ 24h 00 min.) Sets the duration of the 

Energy Saving cycle on workdays.  

ISE 

Energy Saving cycle start on holidays

. (0 ÷ 23h 50 min.) 

dSE 

Energy Saving cycle length on holidays

 (0 ÷ 24h 00 min.) 

TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC) 
Ld1÷Ld6 Workday defrost start

 (0 ÷ 23h 50 min.) These parameters set the beginning of the 6 

programmable defrost cycles during workdays. Ex. When 

Ld2

 = 12.4 the second defrost starts 

at 12.40 during workdays.  

Sd1÷Sd6 Holiday defrost start

 (0 ÷ 23h 50 min.) These parameters set the beginning of the 6 

programmable defrost cycles on holidays. Ex. When 

Sd2

 = 3.4 the second defrost starts at 

3.40 on holidays.  

N.B. :To disable a defrost cycle set it to “nu”(not used). 

Ex. 

 If

 Ld6

=nu

 ; 

 the sixth defrost 

cycle is disabled 

OTHER 
Adr   Serial  address

 (1÷244): Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

Summary of Contents for 6040 Series

Page 1: ...Refrigerated Pastry Showcase 6040 SERIES Maintenance And Use Manual CIAMspa 06081 Petrignano d Assisi PG Italy tel 075 80161 Fax 075 8016215 http www ciamgroup it e mail info ciamgroup it...

Page 2: ...or refrigerators freezers and ice machines 1 4 RESPONSIBILITY Ciam declines any responsibility relevant to damages on persons animals and or products in case of No respect of in force norms Installati...

Page 3: ...ong stock have not to be ascribed to the manufacturer 3 4 DISPLAY CABINET POSITION The refrigerated display cabinet needs particular environmental conditions in order to offer the right performance so...

Page 4: ...et in order to make easy any type of check and maintenance operations When the condensing units are external will be necessary a frame holder that has to be fixed in a proper way and eventually added...

Page 5: ...a wet cloth weekly Additional defrost Under particular conditions of temperature and humidity the frost that normally forms on the evaporator and fans might increase in volume so leading to a faulty f...

Page 6: ...G ELEMENT SUCTION AIR GLASS HEATING ELEMENT OUTLET AIR HEATING ELEMENT REAR GLASS HEATING ELEMENT INTERNAL GLASS HEATING ELEMENT FRONT GLASS UPPER FRAME HEATING ELEMENT FRONT GLASS LATERAL LOWER FRAME...

Page 7: ......

Page 8: ......

Page 9: ...s length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTROL OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C_n fans will switch ON...

Page 10: ...THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA Each parameter present in the HIDDEN MENU can be removed or put into THE FIRST LEVEL user level by pressing SET n In HIDDEN MENU when a parameter is p...

Page 11: ...ture alarm delay 0 255 min time interval between the detection of an alarm condition and alarm signalling dAO Exclusion of temperature alarm at start up from 0 0 min to 23 5h time interval between the...

Page 12: ...TORING SYSTEMS The TTL serial line available through the HOT KEY connector allows by means of the external TTL RS485 converter XJ485 CX to connect the instrument to a monitoring system ModBUS RTU comp...

Page 13: ...ous cycle duration 0 0 24 0h 0 0 Pr2 CCS Set point for continuous cycle 55 0 150 0 C 67 302 F 5 Pr2 COn Compressor ON time with faulty probe 0 255 min 15 Pr2 COF Compressor OFF time with faulty probe...

Page 14: ...50 min nu 13 0 rtc Sd3 3rd holiday defrost start 0 23h 50 min nu 21 0 rtc Sd4 4th holiday defrost start 0 23h 50 min nu 0 0 rtc Sd5 5th holiday defrost start 0 23h 50 min nu 0 0 rtc Sd6 6th holiday de...

Page 15: ...standard way for controller without RTC with EdF rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld6 on workdays and in Sd1 Sd6 in holidays Other parameters are u...

Page 16: ...visualization rEd X REP display optional P1 P2 P3 P4 SET dtr it selects which probe is displayed by X REP P1 Thermostat probe P2 Evaporator probe P3 Third probe only for model with this option enabled...

Page 17: ...will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 8 6 INVERSION OF THE KIND OF ACTION HEATING COOLING i1F Htr This function all...

Page 18: ...XW20LS DIRECT CONNECTIONS OF LOAD Supply 120Vac or 24Vac connect to terminals 5 6 The X REP output is optional 17 DEFAULT SETTING VALUES Label Name Range C F Level Set Set point LS US 3 0 rtc Real tim...

Page 19: ...start 0 23h 50 min nu 0 0 rtc Sd6 6th holiday defrost start 0 23h 50 min nu 0 0 rtc Adr Serial address 1 247 1 Pr2 PbC Kind of probe Ptc ntc ntc Pr2 onF on off key enabling nu oFF ES oFF Pr2 dP1 Room...

Reviews: