ZRMV
高压固态软起动装置说明书
User’s Manual for ZRMV High Voltage Solid Soft Starter
36
6.2
故障代码
故障代码
故障代码
故障代码(
(
(
(
Fault code
)
)
)
)
软起动装置有多种保护功能,当软起动装置保护功能动作时,软起动装置立即停机,
LCD
液晶显示屏
\
触摸屏
\
装置面板上将显示当前故障信息。用户可根据故障内容进行故障分析。
The soft starter has multiple protective functions. When the protective functions act, the soft starter will stop
immediately and the current fault information will be displayed on LCD screen, touch screen and panel. Users can
analyze and clear faults according to fault information.
故障代码
故障代码
故障代码
故障代码
Fault code
故障名称
故障名称
故障名称
故障名称
Fault
故障原因
故障原因
故障原因
故障原因
Cause
处理方法
处理方法
处理方法
处理方法
Troubleshooting
01
系统故障
system failure
系统故障
system failure
联系供货商或生产商
Contact the supplier or manufacturer
02
主电源缺相
Primary power
phase loss
在起动或进行中缺相?
Phase loss in starting or
operation.
检查三相电源是否可靠
Check the reliability of three-phase
power
03
运行过流
Over-current in
operation
负载突然加重?
负载波动太大?
Load suddenly becomes heavy.
Load variation is too large.
调整负载运行状况
调整
F13
项
Adjust load running state
Adjust F13
04
起动超时
Start timeout
负载过重起动时间太短?限
流幅制过小?
Overburdened and start time is
too short.
Current limiting amplitude is
too small.
调整斜坡时间
F03
时间项
调整电流限幅制
F04
项
Adjust ramp time F03
Adjust current limiting amplitude F04
05
相电流不平衡
Unbalanced phase
current
缺相或相电压不平衡,
Phase loss or phase voltage is
unbalanced
调整
F12
项
Adjust F12
06
电子热过载
Electronic thermal
overload
大电流持续时间过长
是否超载运行?
The duration of heavy current
is too long.
Overload operation or not.
检查功能项电机电流设置是否有
误?
是否超载
?
Check if motor current is wrongly set.
Overload or not.
07
内部禁止
Internal
prohibition
违反操作规程
Violate operating instruction
确认操作规程
Ensure operating instruction
08
相序错误
Phase sequence
error
相序接反
Phase sequence reservedly
connected.
调整相序或设置为不检测相序
Adjust phase sequence or set phase
sequence free of check.
6.3
故障记录
故障记录
故障记录
故障记录(
(
(
(
Fault history
)
)
)
)
起动装置最多可记录最近
15