Chapter 1
Introduction to Product
1.6 Technical Indications
Item
Item Description
Input
Power
Supply
Input Voltage
Frequency
Adaptive Motor
Starting Times
Control Modes
Start Modes
Stop Modes
Protective
Functions
Three-phase 380V-15%
415+10%
50/60Hz
Squirrel-cage three-phase asynchronous motor
It is recommended not to exceed 20 times per hour
1) Operation panel control; 2) Operation panel + external
control; 3) External control; 4) External c COM
control; 5) Operation panel + ex COM control; 6)
Operation panel + COM control; 7) COM control; 8) No start
or stop operation.
1) Current-limiting start; 2) Voltage ramp start; 3) Kick
start + current-limiting start; 4) Kick start + voltage
ramp start; 5) Current ramp start; 6) Voltage current-
limiting double closed-loop start.
1) Soft stop; 2) Free stop.
1) Open loop protection for external instantaneous stop terminals; 2)
Over-heat protection for soft starter; 3) Protection for too long starting
time; 4) Input open phase protection; 5) Output open-phase protection;
6) Unbalanced three-phase protection; 7) starting overcurrent
protection; 8) Running overload protection; 9) Undervoltage protection
for power voltage; 10) Overvoltage protection for power voltage; 11)
Protection for fault parameter setting; 12) Load short circuit protection;
13) Auto restart or incorrect wiring protection; 14) Incorrect wiring
protection of external control stop terminals.
A
m
b
ie
n
t
Structure
Place to be
used
Altitude
Ambient
Temperature
Ambient
Humidity
Vibration
Protection
Class
Cooling
Pattern
Indoor location with good ventilation free from corrosive gas
and conductive dust.
Below 1,000M. Derating should be performed before use
if the altitude is higher than 1,000M.
-10
+40
90%RH without dew condensation.
<0.5G
IP20
Natural wind cooling.
Chapter 2 Installation and Wiring
2.1 Operating Conditions
Use the motor soft starter in the following environmental conditions:
Altitude: Maximum 1000m above sea level. Derating should be performed
before use if the altitude is higher than 1,000M.
Ambient Temperature: -10~+40
Ambient Humidity: =90% RH (Non-condensing)
Place to be used: Indoor places free from direct exposure to sunlight, dust,
corrosive gas, flammable gas, oil mist, steam, drip and salt.
Vibration: < 0.5G
Starting Times: =20 times per hour.
2.2 Installation
The motor soft starter shall be installed vertically. DO NOT turn upside
down, lay diagonally or horizontally while installing. Be sure the base is
fixed solidly and evenly.
To get better cooling effect and for the convenience of maintenance,
the motor soft starter shall be installed with enough space left, refer to the
figure below.
Unit in the Figure: mm
Air Outlet
Air Inlet