Chapter 5  Description of Function Parameters

5.2 Detailed Description of Function Parameters

Functional Code P0  Inception Voltage  Setting Range: 30~70%  Factory Default Setting: 30%

Functional description: This function is used to set the voltage value of motor soft starter when 
it is being started.
Note: Voltage ramp mode is enabled; Set the code P7 to "1", the value can be modified; Set P7 to 
"0",. the inception voltage will be 40%.

Functional Code P1   Soft Starting Time   Setting Range: 2~60S  Factory Default Setting: 16S

Functional description: This function is used to set the time spent by the motor from inception 
voltage to rated voltage.
Note: Voltage ramp mode is enabled; Set the code P7 to "1", the value can be modified.

Functional Code P2  Soft Stop Time  Setting Range: 0~60S  Factory Default Setting: 00

Functional description: This function is used to set the time spent by the motor from 
being just stopped at rated speed to full stop. Set this value to "0", there is a free stop.
Note: There are two stop modes for motor soft starter: soft stop and free stop. If the 
machine has an one-to-multi system, then set the value to "0".

1

Soft Stop

 If the code P2 is not set to "0", then soft stop mode is selected. The figure below is the 

output current waveform in the mode of soft stop. Under this condition, the motor is 
powered by a thyristor shifted from a bypass contactor to a soft starter; the output 
voltage of this soft starter gradually decreased from full voltage till it stops completely, 
thus the motor decelerates smoothly and mechanical oscillation can be avoided. The 
output cut-off voltage of soft stop is equal to the Inception Voltage.

 In the mode of soft stop, surf of water pump loads can be reduced or even removed, 

and large current impulse caused by soft stop can be reduced. The current limitation 
value of soft stop is a percentage reckoned on the starting current-limiting value.

Chapter 5  Description of Function Parameters

2

Free Stop

 If the code P2 is set to "0", then free stop mode is selected.

In this stop mode, once stop command is received, the soft starter will disconnect the 
bypass contactor and disable voltage output of the thyristor. Then the motor will 
gradually shutdown due to load inertia. To avoid open phase error report, P2 should be 
set to this mode if the soft starter adopts one-to-multi wiring method.

 To extend the service life of soft starter, free stop mode is generally preferred if there 

is no need to adopt soft stop mode. In free stop mode, instantaneous output is 
completely disabled, thus instantaneous impulse of heavy current can be avoided. ZJR1 
series of soft starters provide 6 working modes applicable to various kinds of motors 
and loads. So users should choose a proper one according to different applications.

Functional Code P3  Starting Limitation Current  Setting Range: 50~500% Default Setting: 400%

Functional description: This function is used to set the peak output current value of a 
motor soft starter when it is starting. The formula is: set value 

 motor rated current 

(Function PC)= peak current (unit: A) that is limited by a motor softer starter to be output.
Note: Current limiting mode enabled; If the code P7 is set to "0", the modification will be 
valid; If P7 is set to "1", the current limiting value will be 400%.

Functional Code P4  Max. Working Current  Setting Range: 50~200%  Default Setting: 100%

Functional description: Maximum working current refers to maximum current 
performing sustainable operation whose value is reckoned on the basis of the set 
value in the functional code PC. If the current exceeds the max value, there will be an 
inverse-time thermal relief protection.
Note: Modification will be valid if the code P7 is set to "0".

Functional Code P5  Undervoltage Protection  Setting Range: 60~90%  Default Setting: 80%

Functional description: When the actual working voltage is lower than the set 
value, then protection for motor soft starter is disabled and the LED display F09.

Functional Code P6  Overvoltage Protection  Setting Range: 100~130%  Default Setting: 120%

Functional description: When the actual working voltage is higher than the set 
value, then protection for the motor soft starter is disabled and the LED display F10.

Functional Code P7   Starting Mode   Setting Range: 00~05   Default Setting: 01

1) Current-limiting Start

 If the code P7 is set to "0" (indicating current limiting), then current starting 

mode is selected. The figure below is a current change waveform of a motor in the 
mode of current-limiting start. "l1" in the figure refers to the set value of starting 
current-limiting. When the motor starts, the output voltage will rise rapidly till the 
motor current reaches the set current-limiting value "l1" and

Summary of Contents for ZJR1 Series

Page 1: ...ZJR1 SERIES SOFTSTART USER S MANUAL...

Page 2: ...ty Instructions 1 1 2 Product Inspection upon Arrival 2 1 3 Demonstration of the Specifications Label and Model 2 1 4 Outline of the Product 3 1 5 Models and Specifications 4 1 6 Technical Indications...

Page 3: ...ails in the input and output ports with insulated sheath or tape When the motor soft starter is under remote control do lock the keyboard control to avoid accidence due to error operation Do cut off t...

Page 4: ...W Nameplate Base Circuit Board Cabinet Connect to the bypass contactor L21 L22 L23 Input Terminals of Power Supply R S T Operation Panel Base Control Terminal Connect to the motor U V W Circuit Board...

Page 5: ...rameter setting 12 Load shortcircuit protection 13 Autorestart or incorrectwiring protection 14 Incorrect wiring protection of external control stopterminals Ambient Structure Place to be used Altitud...

Page 6: ...cuit power supply or install an electromagnetic contactor between the input terminals R S T and the power supply to run or stop the motor soft starter Do select RUN or STOP keys on the operation panel...

Page 7: ...k Terminal Name Functional Description Bypass Output Operation Output Delayed Switch on 01 and 02 after soft starter is completely started to control bypass contactor 03 and 04 indicate programmable r...

Page 8: ...Start Common Port Switch K on motor starts switch K off motor stops Chapter 2 Installation and Wiring Instantaneous Stop Stop Start Common Port Instantaneous Stop Stop Start Common Port 2 3 6 Relay N...

Page 9: ...ne stops completely 2 This key also performs the function of failure state resetting When REAdy is displayed press this key to set the manual When P0030 is displayed repress this key When flashes pres...

Page 10: ...regardless of successor failure Note H1 H9 refer to save 9 recently occurred failure tips in a recursive way If entering setting mode in none soft start stop mode you may get tips Press then press to...

Page 11: ...he current limiting value code P3 indicating current mode enabled to raise the torque Be sure the motor rotates in the correct direction Only after making sure there is no anomaly can the motor be put...

Page 12: ...error report P2should be set to thismode if thesoft starter adoptsone to multi wiring method To extend the servicelife of softstarter free stop mode isgenerally preferred ifthere is no needto adopt so...

Page 13: ...oltage but not through the mechanical control over time t regardless of whether the motor is accelerated steadily Therefore if there is a light load the starting time will tend to be less than the set...

Page 14: ...rammable output external terminals changes from open toclose that is reversed phase output Flexible use ofprogrammable relay output functions cansimplify external control logic circuit Chapter 5 Descr...

Page 15: ...the decisiondatum deviation willbe enhanced Overcurrent Starting ProtectionTime Thisrefers to theprotection time thatis successively 5 timeslonger than themaximum working currentset by thecode P4 See...

Page 16: ...atment Fault cleared Faults such as undervoltage overvoltage overcurrent instantaneous terminal open etc have been eliminated Everything turns to normal and now the LED ready lights up indicating the...

Page 17: ...tableabove are themaximum values ofa soft starter Generally ratedcurrent matching themotor that hassame power shouldnot excess therated current values listedin this table If outline sizesdiffer from t...

Page 18: ...uality problem or accident we merely promise to bear the above mentioned responsibilities Ifa user needs more guarantees for liabilities please assure on the insurance company voluntarily Appendix 1 V...

Reviews: