Warning! If not avoided, the following could result in death or serious injury.
•
Always connect the ground or earth first to reduce shock hazard.
•
FIRE HAZARD! Do not use a power cord, harness, or cable that appears damaged.
•
FIRE AND SHOCK HAZARD! Do not attempt operation unless the power cord, power socket, and
power plug meet the appropriate local rating standards.
•
SHOCK HAZARD! Do not attempt operation if the AC supply is not within the specified voltage
and current, as specified on the license label.
•
SHOCK HAZARD! A dedicated, protected ground or earth wire must be installed on the product
by Christie qualified technicians or electricians before it can be connected to power.
•
A certified electrician must be present during installation to ensure the installation meets the
local electrical code.
Caution! If not avoided, the following could result in minor or moderate injury.
•
Use an appropriately sized strain relief connector with the knockout plate provided, to ensure
adequate environmental sealing and to prevent the AC supply cable from accidentally being torn
out or rubbing against the knockout plate.
•
A 30 A maximum rated, certified wall circuit breaker is required. It must be part of the building
and easily accessible.
•
Use a minimum of 12 AWG copper wire, grounding included, for the connection of the main AC
supply to the projector's ground lug.
•
Either copper or aluminum is acceptable as conductor wiring material to the terminal block.
A
UPS circuit breaker
B
MAIN input circuit breaker
C
200-240 V main inlet
Installing and setting up
C 4K-RGB Installation and Setup Guide–CP4415-RGB, CP4420-RGB
20
020-103244-04 Rev. 1 (03-2021)