1.3 GENERAL SPECIFICATIONS
Sodium hypochlorite production:
NEXGEN50R – Up to 60 pounds per day
Maximum pool return line pressure:
25 PSI including plumbing to and from the venturi injector
Electrical requirements:
NEXGEN50 and 50R
Rated 208-240 VAC, 45.87 A, 50/60 Hz.
Requires:
A 208-240 volt single phase connection @ 60 amps minimum and 50 or 60Hz
120 volt connection to a chemical feed controller or 120 volt outlet @1 amp
Certifications
NEXGEN50R is certified for indoor installation.
NSF Standard 50
UL Standard 1081
CSA Standard C22.2 #218.1
PRMA Reg. No. 33004
Sizing guidelines
Chlorinator sizing must comply with local codes. Please contact your local health
department for specific requirements or contact your local ChlorKing representative for