SM Install Manual
Page 18 of 35
05/05/2016
15.0 Through 25.0: 208/240V Only
Connect the blue control cord to a chemical feed controller or for manual operation, to a 120
volt AC outlet. When connecting to a chemical feed controller, be sure the controller is set to
continuous feed and not set on proportional control. Proportional control will reduce the life of
power supply components.
Connect the four pin salt sensor connector to the four pin connector labeled SALT SENSOR.
Connect the two pin flow switch connector to the two pin terminal labeled FLOW SWITCH.
The terminal labeled FEED SALT is used with the optional Saturated Salt Feeder. When using
the optional Salt Feeder, plug the cable from the Saturated Salt Feeder Relay Box to the
terminal marked FEED SALT.
Connect the red connector from the power supply to the red connector on the cell.
NOTE:
Never remove the cables from the top of the cell. Always disconnect the cell with the
red connector.
Ground
(Green)
Line 1
(Black)
Line 2
(Red)