Typical battery backup times
By combining UPS and battery extensions (BP), the typical backup times
achieved with new, fully loaded batteries listed in the following table can be
achieved (all listed autonomy times in min).
VA
Watt
ACTIVE
700(-19)
ACTIVE
1000(-19)
ACTIVE
1000(-19) + 1 BP
ACTIVE
1000(-19) + 2 BP
100
70
33
63
242
452
200
140
23
36
139
261
300
210
14,5
27
95
178
350
245
12
24
86
152
400
280
10,5
20
71
133
500
350
9
15
56
105
600
420
7
12
46
86
700
490
6
10
39
72
800
560
8,5
33
62
1000
700
7
28
48
Table 17: Backup times ACTIVE 700(-19) and ACTIVE 1000(-19)
VA
Watt
ACTIVE 2000
ACTIVE
2000-19
+ 1 BP
ACTIVE
2000-19
+ 2 BP
ACTIVE 2000
+ 1 BP
ACTIVE
2000-19
+ 3 BP
ACTIVE
2000-19
+ 4 BP
ACTIVE 2000
+ 2 BP
ACTIVE
2000-19
+ 5 BP
400
280
62
145
238
338
445
500
350
51
119
193
278
366
600
420
43
100
164
233
307
700
490
36
84
138
196
258
800
560
31
72
119
169
222
1000
700
24
51
84
119
157
1250
875
19
43
71
102
133
1500
1050
16
35
56
80
105
1750
1225
13
28
48
68
89
2000
1400
10
24
37
53
69
Table 18: Backup times ACTIVE 2000(-19)