Interface description

CHLORIDE ACTIVE

GB - 34

V02OCT/01

945040.066

BYPASS ACTIVE

(N.O. between 1 and 4)

This signal is active when the device has been switched to bypass, the
inverter is blocked and the power is supplied from the mains supply.

SUM ALARM

(N.O. between 8 and 4)

This output is active when one of the messages "AC FAIL", "BATT LOW" or
"BYPASS ACTIVE" has been output or the "ALARM" display on the front
side illuminates.

The contact rating of the signalling contacts is 1 A / 24 V DC or
1 A  /  120 V AC.

In addition, an isolated auxiliary voltage 12 V DC is made available (pin 9:
+12 V, 50 mA; pin 7: GND)

EXT. OUTLETS CONTROL interface 

The UPS is capable of switching specific connected loads through the EXT.
OUTLETS CONTROL interface. In combination with an output distributor
(ECO), available as an accessory, it is thus possible to operate a load man-
agement system. For a description of the functionality, please refer to the
operating instructions included with the output distributor.

Summary of Contents for ACTIVE 1000-19

Page 1: ...o Istruzioni per l uso Manual de instruções Unterbrechungsfreie Stromversorgung Uninterruptible Power System Alimentation Sans Interruption Sistema de Alimentación Ininterrumpida Gruppo di continuità Sistema ininterrupto de alimentação TOWER DFWLYH DFWLYH DFWLYH DFWLYH RACK DFWLYH DFWLYH DFWLYH DFWLYH ...

Page 2: ......

Page 3: ...on Sistema de Alimentación Ininterrumpida Gruppo di continuità Sistema ininterrupto de alimentação TOWER RACK DFWLYH DFWLYH DFWLYH DFWLYH DFWLYH DFWLYH DFWLYH DFWLYH Bedienungsanleitung Operating Manual Manuel utilisateur Instrucciones de servicio Istruzioni per l uso Manual de instruções 25 219 4 2416 6 10 ...

Page 4: ...te en caso de la concesión de patentes o de modelos de utilidad Entrega sometida a disponibilidad Reservado el derecho de establecer modificaciones téc nicas F E All rights including rights of translation re production by printing copying or similar me thods even of parts are reserved Offenders will be liable for damages All rights including rights created by patent grant or registration of utilit...

Page 5: ... side rack mounting devices GB 15 Models ACTIVE 700 19 and ACTIVE 1000 19 GB 15 Models ACTIVE 2000 19 and ACTIVE 3000 19 GB 17 Installation and commissioning GB 19 Installation notes for rack mounting devices GB 19 Selecting the installation site GB 19 Mechanical fixing GB 20 Installing the UPS devices GB 21 Commissioning the UPS devices GB 22 Commissioning of an external battery extension GB 23 S...

Page 6: ...onal COM interface GB 32 EXT OUTLETS CONTROL interface GB 34 Maintenance GB 35 Storage GB 35 Cleaning GB 36 Troubleshooting GB 37 Technical data GB 39 Technical data for the models ACTIVE 700 to ACTIVE 3000 GB 39 Technical data for the models ACTIVE 700 19 to ACTIVE 3000 19 GB 42 Usable Battery lifetime GB 45 Typical battery backup times GB 46 ...

Page 7: ...ons GB 24 Number of external battery extensions GB 26 UPS control panel in normal operation GB 29 UPS control panel in battery operation GB 30 UPS control panel in bypass operation GB 30 COM 3 interface GB 31 COM 1 interface GB 33 Rectification of errors GB 37 Electrical data ACTIVE 700 to ACTIVE 3000 GB 39 General data ACTIVE 700 to ACTIVE 3000 GB 40 Mechanical data ACTIVE 700 to ACTIVE 3000 GB 4...

Page 8: ... end of this manual The contents of these operating instructions shall not become part of or modify any prior agreement commitment or relationship The sales contract contains the entire obligations of CHLORIDE The warranty contained in the contract between the parties is the sole warranty of Any statements contained herein do not create any new warranties or modify the existing warranty Warning Ca...

Page 9: ...cles Housing Designation Order No Nominal power Tower upright device ACTIVE 700 570219 200 700 VA ACTIVE 1000 570220 200 1000 VA ACTIVE 2000 570221 200 2000 VA ACTIVE 3000 570222 200 3000 VA Rack rack mounting device ACTIVE 700 19 570223 200 700 VA ACTIVE 1000 19 570224 200 1000 VA ACTIVE 2000 19 570225 200 2000 VA ACTIVE 3000 19 570226 200 3000 VA Table 1 Overview of UPS devices Housing Designati...

Page 10: ... EWG and 93 68 EWG Conformity is established through compliance with the following standards EN 50091 1 1 1996 EN 50091 2 1995 Additional information regarding adherence to these directives is included in the appendices NSR and EMC of the EU Declaration of Conformity If needed the EU Declaration of Conformity can be requested from CHLORIDE Symbols and pictograms The following symbols and pictogram...

Page 11: ...a cold environment moisture conden sation can occur Before commissioning the device it must be com pletely dry For this reason an acclimation time of at least two hours is required When selecting a location for the device and during commissioning observe the notices concerning environmental conditions given in chapter Technical data on page GB 39 Rack mounting devices as well as the corresponding ...

Page 12: ...rating ele ments or mains lines penetration of fluids or foreign bodies switch off the device pull the mains plug and contact the responsible customer service representative Repair work may only be carried out by authorised personnel Unau thorised opening and improper repairs can expose the user to serious danger Do not connect any devices which overload the UPS e g laser printer or vacuum cleaner...

Page 13: ...our computer system until mains voltage has been restored In the event of an extended mains failure you should nevertheless store your data and discon tinue your work You will be alerted by means of acoustical buzzer and optical LED alarms contained in the UPS that a mains failure has occurred or is occurring Listed below are procedures which are intended to assist you in determining how critical ...

Page 14: ...g on the user program operating system and computer hardware you can ensure that during a mains failure user programs are automatically closed users logged into the server are logged off data are saved and the operating system is shutdown For further information you are referred at this point to the documentation for the CHLORIDE commu nication software After mains voltage is restored the UPS auto...

Page 15: ...interruption directly by the mains supply via the automatic bypass As soon as normal operating conditions are restored the system automatically switches back to inverter operation Below the symbols located on the front side of the UPS are shown and described Fig 1 Symbols on the front side of the UPS LOAD BYPASS INVERTER BATTERY MAINS ALARM ...

Page 16: ...lluminates when the UPS is in a faulty state An acoustical warning signal is output at the same time this signal is reset when the UPS is switched off The button switches the inverter off and the bypass on The button switches on the inverter The inverter is activated upon activation of the button Following a delay time of approx 5 seconds the BYPASS indicator extinguishes and the INVERTER indicato...

Page 17: ...AC INPUT Input fuse The fuse must only be changed when the device is switched off and the mains con nection cable disconnected COM 3 interface COM interface optional EXT OUTLETS CONTROL interface USB interface Connection for battery extension Fan Output sockets AC OUTPUT Mains connection AC INPUT Input fuse The fuse must only be changed when the device is switched off and the mains con nection cab...

Page 18: ...ce COM 3 interface Connection for battery extension Fan Output sockets AC OUTPUT Input circuit breaker Mains connection AC INPUT EXT OUTLETS CONTROL interface COM interface optional USB interface COM 3 interface Connection for battery extension Fan Output sockets AC OUTPUT Input circuit breaker Mains connection AC INPUT Fig 5 Rear side ACTIVE 2000 Fig 6 Rear side ACTIVE 3000 ...

Page 19: ...e following legend applies to figures Fig 7 and Fig 8 1 Mains connection AC INPUT 2 Output sockets AC OUTPUT 3 Input fuse The fuse must only be changed when the device is switched off and the mains connection cable disconnected 4 Interface COM 3 5 Interface USB 6 Interface EXT OUTLETS CONTROL 7 Fan 8 COM interface optional 9 Nameplate 10 Battery extension cable not with ACTIVE 700 19 11 Connection...

Page 20: ...B 16 V02OCT 01 945040 066 Fig 8 Rear side ACTIVE 1000 19 and battery extension Notice To connect the BPACTIVE1000 19 battery extension to the UPS ACTIVE 1000 19 use the separate cable 10 provided in the delivery contents ACTIVE 1000 19 BPACTIVE1000 19 ...

Page 21: ... 10 1 Mains connection AC INPUT 2 Output sockets AC OUTPUT 3 Input circuit breaker 4 Interface COM 3 5 Interface USB 6 Interface EXT OUTLETS CONTROL 7 Fan 8 COM interface optional 9 Nameplate 10 Battery extension cable permanently mounted 11 Connection for battery extension 12 Battery switch Fig 9 Rear side ACTIVE 2000 19 and battery extension ACTIVE 2000 19 BPACTIVE3000 19 ...

Page 22: ...TIVE3000 19 battery extension are two battery extension cables The first extension is connected to battery cable 10 of the UPS each additional exten sion is connected via the two aforementioned cables Protection against polarity reversal at the battery extensions is ensured through the coding of the plug 10 on the UPS device and the connection socket 11 ACTIVE 3000 19 BPACTIVE3000 19 ...

Page 23: ...nection for the UPS output Communication software CD RS 232 interface cable Installation notes for rack mounting devices Selecting the installation site All rack mounting devices ACTIVE 19 are intended for horizontal instal lation in 19 inch cubicles Notice When installing the UPS bear in mind the large weight of the individ ual components For weight purposes mount the devices as low as possible i...

Page 24: ...llation rails When used these allow the device to be easily inserted into and pulled out of a 2 HU installation slot Fig 11 Installing the slide rails on the UPS or battery extension Slide rails for the installation in cubicles are available as accessories for var ious cubicle systems To fix the device in the horizontal position the front plate has to be fixed to the 19 inch cubicle at the indicat...

Page 25: ...nnected to the AC mains supply voltage is available at the output sockets AC OUTPUT even when the UPS is not switched on via the button on the front side The MAINS and BYPASS LEDs illuminate Danger Keep the air inlet and outlet openings on the rear and front sides of the device free of obstruction Do not operate the device or the bat tery packs upside down or on their sides Notice For proper opera...

Page 26: ...omputer system Observe any additional notices provided in the material supplied with your accessory Switch on your loads Now switch on the UPS by pressing the button on the front side In addition to the MAINS and BYPASS indicators the LOAD output load indicator now illuminates After a few seconds the INVERTER indi cator also illuminates and the BYPASS indicator extinguishes The UPS now operates in...

Page 27: ...vice and five battery extensions to the ACTIVE 2000 19 and ACTIVE 3000 19 UPS devices Danger Make certain that the circuit breaker on the battery extension is in the OFF position For models ACTIVE 1000 19 to ACTIVE 3000 19 connect the battery extension to the UPS using the supplied cable The arrangement of the connection cable is shown in the following figures using the upright device as an exampl...

Page 28: ...CTIVE 2000 19 and ACTIVE 3000 19 Notice Please note that the ACTIVE 2000 19 and ACTIVE 3000 19 devices do not contain internal batteries Therefore during commissioning of the first connected BPACTIVE3000 19 battery they do not provide protection against mains failure If no battery is connected to the device an alarm is output To cancel the alarm move the battery circuit breaker to the ON position ...

Page 29: ... externally connected battery extensions Proceed as follows Press the button to switch the UPS to BYPASS operation Press the button again and do not release it until the UPS emits an acoustical signal After you have released the button all LEDs on the BATTERY indicator flash twice The current setting for the number of externally connected bat tery extensions is then displayed The possible displays...

Page 30: ... of external battery extensions Notice Upon conclusion of the adjustment procedure the UPS is in bypass operation Switch the UPS to online operation by pressing the but ton for at least 1 second Capacity in 0 B a t t e r y e x t e n s i o n s 1 B a t t e r y e x t e n s i o n 2 B a t t e r y e x t e n s i o n s 3 B a t t e r y e x t e n s i o n s 4 B a t t e r y e x t e n s i o n s 5 B a t t e r y...

Page 31: ...end of the backup time If this is not the case refer to chapter Troubleshooting on page GB 37 Reconnect the UPS to mains Your UPS is now again ready for operation Note that the batteries must be recharged before the full backup time is again available Automatic test Lamp test While the device is connected to mains press the button for at least 1 second in order to switch the device to bypass opera...

Page 32: ...device must be in online operation With the device connected to mains press the button for at least 1 second The input is confirmed by a single acoustical signal and the connected load is now supplied by the battery for 10 seconds The elements of the BATTERY LED strip correspond to the charging state of the battery and the LOAD LED strip corresponds to the load factor The MAINS and INVERTER indica...

Page 33: ... V02OCT 01 GB 29 G B Operating modes The UPS has three different operating modes when it is switched on Normal operation mains supply present The loads are supplied directly from mains via the inverter I I Fig 14 UPS control panel in normal operation ...

Page 34: ...ls of approx 4 seconds If the minimum power level of the battery is reached the signal is emitted every second Bypass operation overload 130 In the event of a large overload 130 the device switches to bypass and the inverter is blocked Power is supplied by the mains supply This is not a normal operating state If the mains supply fails the loads are no longer supplied no UPS operation I I Fig 15 UP...

Page 35: ...ng switchable load distributors ECO The interfaces can be used for direct communication between UPS and computer integrating the UPS as a client into a network with central monitoring SNMP passing on operating states to external message systems load management by means of switchable load distributors The necessary communication software packets interface cards and exten sion modules are available ...

Page 36: ... USB interface is used for communication purposes the COM 3 interface is not operational Optional COM interface The optional COM interface can be fitted with various interface cards The code located next to the plug is then dependent on the interface card model A detailed description is included with the various interface cards which are available as accessories Possible interface cards SNMP adapt...

Page 37: ...nal state AC FAIL N O between pins 2 and 4 N C between pins 3 and 4 This signal is active when the mains voltage at the UPS input is not present for at least 10 seconds or the mains voltage exits the tolerance range The signal is cancelled 850 ms following mains restoration BATT LOW N O between 5 and 4 This output is active when the battery can continue to supply current at the nominal load for on...

Page 38: ...lay on the front side illuminates The contact rating of the signalling contacts is 1 A 24 V DC or 1 A 120 V AC In addition an isolated auxiliary voltage 12 V DC is made available pin 9 12 V 50 mA pin 7 GND EXT OUTLETS CONTROL interface The UPS is capable of switching specific connected loads through the EXT OUTLETS CONTROL interface In combination with an output distributor ECO available as an acc...

Page 39: ...In addition an acoustical signal is emitted every minute Check whether the backup time of the UPS is still adequate for your application see Checking the operational readiness in regular intervals 6 12 months Storage When storing for longer periods in regions with moderate climates the bat teries should be charged every 3 months for 5 hours In areas with higher temperatures this interval should be...

Page 40: ...S by pressing the button and pull the mains plug out of the sock et When cleaning do not use scouring agents or cleaning agents which are damaging to plastics Make certain that no fluids enter the interior of the UPS Make certain that the ventilation slits on the UPS remain open The surface of the UPS housing can be cleaned with either a dry or damp cloth ...

Page 41: ... electrician Input fuse defective or input circuit breaker tripped Replace with fuse of same type or switch on circuit breaker If the prob lem persists contact the responsible customer service representative MAINS indicator does not illuminate acousti cal alarm sounds in intervals No mains voltage present UPS operation see Operational behaviour on page GB 27 MAINS indicator flashes Phase and neutr...

Page 42: ...ontact the responsible customer service representative Batteries are defective Contact customer service Charging device is defective Contact customer service OVERLOAD LED illumi nates Overload at UPS output Reduce load to the permissible value No communication between UPS and PC Wrong serial connection cable Check whether the correct cable has been used standard modem null modem cables are not per...

Page 43: ...d maintenance free Voltage V 24 36 96 96 Autonomy time half load full load min 12 6 15 7 24 10 14 6 Autonomy time 1 battery exten sion half load full load min 56 28 84 37 52 25 Autonomy time 2 battery exten sions half load full load min 105 48 157 69 97 43 Output Voltage 1 N AC 220 230 240 V Voltage tolerance 3 Frequency line clocked see Input frequency Frequency self clocked 50 60Hz 0 5 Harmonic ...

Page 44: ... 45 battery operation 40 40 46 46 Perm ambient temperature during operation 10 C to 40 C recommended 15 C to 32 C Perm ambient temperature during storage 15 C to 40 C Perm rel humidity during operation 20 to 90 no condensation perm Installation altitude max 3000m from 1500m max Ambient temperature 35 C Table 8 General data ACTIVE 700 to ACTIVE 3000 UPS model ACTIVE 700 ACTIVE 1000 ACTIVE 2000 ACTI...

Page 45: ... 10 A 10 A 16 A COM 3 interface SUB D 9 pin pins USB interface USB type B COM interface optional SUB D 9 pin socket EXT OUTLETS CONTROL interface SUB D 9 pin socket Battery extension none plug 3 pin Table 10 Connections ACTIVE 700 to ACTIVE 3000 UPS model ACTIVE 700 ACTIVE 1000 ACTIVE 2000 ACTIVE 3000 Signalling LED indicator on front side Acoustical alarm Message Message contacts see SIC option I...

Page 46: ...nal battery exten sions only Voltage V 24 36 96 96 Autonomy time half load full load min 12 6 15 7 Autonomy time 1 battery exten sion half load full load min 56 28 24 10 14 6 Autonomy time 2 battery exten sions half load full load min 105 48 51 24 31 14 Output Voltage 1 N AC 220 230 240 V Voltage tolerance 3 Frequency line clocked see Input frequency Frequency self clocked 50 60Hz 0 5 Harmonic dis...

Page 47: ...ration 40 dB 40 dB 46 dB 46 dB Perm ambient temperature during operation 10 C to 40 C recommended 15 C to 32 C Perm ambient temperature during storage 15 C to 40 C Perm rel humidity during operation 20 to 90 no condensation perm Installation altitude max 3000m from 1500m max Ambient temperature 35 C Table 13 General data ACTIVE 700 19 to ACTIVE 3000 19 UPS model ACTIVE 700 19 ACTIVE 1000 19 ACTIVE...

Page 48: ...ent 10 A 10 A 10 A 16 A COM 3 interface SUB D 9 pin pins USB interface USB type B COM interface optional SUB D 9 pin socket EXT OUTLETS CONTROL interface SUB D 9 pin socket Battery extension none plug 3 pin Table 15 Connections ACTIVE 700 19 to ACTIVE 3000 19 UPS model ACTIVE 700 19 ACTIVE 1000 19 ACTIVE 2000 19 ACTIVE 3000 19 Signalling LED indicator on front side Acoustical alarm Message Signall...

Page 49: ... usable lifetimes of the batteries used in the UPS devices only as a function of the ambient temperature of the devices In addition the usable lifetime is also dependent on the cyclical use of the batteries i e the frequency and duration of mains failures also reduces the usable lifetimes of the batteries Ambient temperature Usable lifetime years ...

Page 50: ...4 86 152 400 280 10 5 20 71 133 500 350 9 15 56 105 600 420 7 12 46 86 700 490 6 10 39 72 800 560 8 5 33 62 1000 700 7 28 48 Table 17 Backup times ACTIVE 700 19 and ACTIVE 1000 19 VA Watt ACTIVE 2000 ACTIVE 2000 19 1 BP ACTIVE 2000 19 2 BP ACTIVE 2000 1 BP ACTIVE 2000 19 3 BP ACTIVE 2000 19 4 BP ACTIVE 2000 2 BP ACTIVE 2000 19 5 BP 400 280 62 145 238 338 445 500 350 51 119 193 278 366 600 420 43 1...

Page 51: ...P ACTIVE 3000 2 BP ACTIVE 3000 19 5 BP 600 420 38 90 148 210 277 700 490 34 80 131 189 248 800 560 29 70 114 163 216 1000 700 22 54 90 128 168 1250 875 19 42 70 100 131 1500 1050 14 31 52 74 97 1750 1225 13 27 47 67 88 2000 1400 11 24 40 56 73 2250 1575 9 22 35 49 65 2500 1750 7 19 30 44 57 2750 1925 6 5 18 26 39 51 3000 2100 6 14 25 32 43 Table 19 Backup times ACTIVE 3000 19 ...

Page 52: ...Technical data CHLORIDE ACTIVE GB 48 V02OCT 01 945040 066 ...

Page 53: ... 120 italy sales chloridepower com AUSTRALIA Chloride Hytek PTY LTD Units C1A and C1B Centrecourt Business Park 25 27 Paul Street North North Ryde NSW 2113 Australia Telephone 61 2 9888 1266 Facsimile 61 2 9888 1966 australia sales chloridepower com FRANCE Chloride Power Protection 1 rue Felix Potin ZA Les Belles Vues 91290 Arpajon France Telephone 33 1 6926 1281 Facsimile 33 1 6083 1816 france sa...

Page 54: ...loride Telecom Systems ZA Les Rolandières 35120 Dol de Bretagne France Telephone 33 299 48 2068 Facsimile 33 299 48 3394 com ce saed com GERMANY Masterguard Schallershofer Str 141 D 91056 Erlangen Germany Telephone 49 9131 9855 100 Facsimile 49 9131 9855 270 info masterguard de ITALY Chloride Silectron Via Fornace 30 40023 Castel Guelfo Bologna Italy Telephone 39 054 2632 111 Facsimile 39 054 2632...

Page 55: ...loridepower com SPAIN Chloride Boar Azufre 8 10 Polígono Industrial Sur 28770 Colmenar Viejo Madrid Spain Telephone 34 91 848 84 00 Facsimile 34 91 845 51 32 spain sales chloridepower com THAILAND Chloride Power Electronics LTD Panjathani Tower 20th Floor 127 25 Nonsee Road Chongnonsee Yannawa Bangkok 10120 Thailand Telephone 662 6810 100 Facsimile 662 6810 109 thailand sales chloridepower com Seb...

Page 56: ...otection George Curl Way Southampton Hampshire SO18 2RY United Kingdom Telephone 44 0 23 8061 0311 Facsimile 44 0 23 8061 0852 sales chloridepower com Oneac UK 18 20 Blacklands Way Abingdon Business Park Abingdon Oxfordshire OX14 1DY United Kingdom Telephone 44 0 1235 534 721 Facsimile 44 0 1235 534 197 oneac_ltd oneac com USA Chloride Power Protection 28430 N Ballard Lake Forest IL 60045 USA Tele...

Page 57: ...80 5124 info oneac com INTERNATIONAL SALES Europe Middle East and Africa Chloride Power Protection George Curl Way Southampton Hampshire SO18 2RY United Kingdom Telephone 44 0 23 8061 0311 Facsimile 44 0 23 8061 0852 international sales chloridepower com Chloride Industrial Middle East CIME PO Box 17693 Dubai United Arab Emirates Telephone 971 4 881 8848 Facsimile 971 4 881 4518 ...

Page 58: ...a Arizona 1349 Brooklin Novo Sao Paulo CEP 04567 002 Brazil Telephone 55 11 5505 4661 Facsimile 55 11 5505 4832 latinamerica sales chloridepower com Asia Pacific Chloride Power Protection 80 Marine Parade Road 10 08 Parkway Parade 449269 Singapore Telephone 65 348 5288 Facsimile 65 348 3400 asiaups chloridepower com ...

Page 59: ...MASTERGUARD ...

Page 60: ...ished by Publié par Publicado por Pubblicato da Editado por CHLORIDE SILECTRON Via Fornace 30 40023 Castel Guelfo Bologna Italy Bestell Nr Order No No de réf Nº de pedido Codice di ord N Nº de encomenda 945040 066 V02OCT 01 ...

Reviews: