Interface description
CHLORIDE ACTIVE
GB - 34
V02OCT/01
945040.066
BYPASS ACTIVE
(N.O. between 1 and 4)
This signal is active when the device has been switched to bypass, the
inverter is blocked and the power is supplied from the mains supply.
SUM ALARM
(N.O. between 8 and 4)
This output is active when one of the messages "AC FAIL", "BATT LOW" or
"BYPASS ACTIVE" has been output or the "ALARM" display on the front
side illuminates.
The contact rating of the signalling contacts is 1 A / 24 V DC or
1 A / 120 V AC.
In addition, an isolated auxiliary voltage 12 V DC is made available (pin 9:
+12 V, 50 mA; pin 7: GND)
EXT. OUTLETS CONTROL interface
The UPS is capable of switching specific connected loads through the EXT.
OUTLETS CONTROL interface. In combination with an output distributor
(ECO), available as an accessory, it is thus possible to operate a load man-
agement system. For a description of the functionality, please refer to the
operating instructions included with the output distributor.