CHLORIDE ACTIVE
Technical data
945040.066
V02OCT/01
GB - 43
G
B
UPS model
ACTIVE
700-19
ACTIVE
1000-19
ACTIVE
2000-19
ACTIVE
3000-19
Electrical safety
EN 50091-1; EN 60950
Radio interference level
EN 50091-2, Class B
Emitted interference
EN 50081-1
Interference immunity
EN 50082-1
IEC 801-2,Level 4 / IEC 801-3,Level 3
IEC 801-4,Level 4 / IEC 801-5,Level 3
Mains pollution
EN 61000-3-2, EN 61000-3-3
Efficiency
> 83 %
90 %
Degree of protection
IP20
Cooling
Fan
Noise level
in dB(A), typical
Mains operation,
40 dB
40 dB
46 dB
46 dB
battery operation
40 dB
40 dB
46 dB
46 dB
Perm. ambient temperature during operation
10°C to + 40°C
recom15°C to + 32°C
Perm. ambient temperature during storage
-15°C to + 40°C
Perm. rel. humidity during operation
20% to 90%, no condensation perm.
Installation altitude
max. 3000m, from 1500m max.
Ambient temperature = 35°C
Table 13: General data (ACTIVE 700-19 to ACTIVE 3000-19)
UPS model
ACTIVE
700-19
ACTIVE
1000-19
ACTIVE
2000-19
ACTIVE
3000-19
UPS
Weight / kg
13
16
10
11
Dimensions / mm
Width
Height
Depth
482,6
87
485
Body size
Dimensions / mm
Width
Height
Depth
410
87
412
Battery extension
Model
BPACTIVE
1000-19
BPACTIVE
3000-19
Weight / kg
21,5
27
Dimensions / mm
Width
Height
Depth
482,6
87
448
Table 14: Mechanical data (ACTIVE 700-19 to ACTIVE 3000-19)