Page 12 of 40
IRIS Touch
Engineering Manual Version 1.4
You must enter Engineer Mode on the Galaxy to access these options.
56 = Communication
4 = Ethernet
01= Module Config
1 = IP Address
- Program in the IP address for the IRIS e.g. 192.168.0.10
2 = Site Name
- Leave blank
3 = Gateway IP
- Enter the network gateway IP address e.g.192.168.0.1
4 = Network Mask
- Enter the subnet mask e.g. 255.255.255.0
Note: If you are using a DHCP address then leave all “Module Config” addresses blank
02 = Alarm Reporting
1 = Format
- Set to SIA level 3
2 = Primary IP
1 = IP Address
- Set this to the IP address of the monitoring centre
e.g. 80.176.196.135
Note: Secondary IP address not required as the backup IP address will be
download by the IRIS Secure Apps system to the dialler.
4 = Account No.
- Enter in the account number allocated by the
monitoring centre.
03 = Remote Access
1 = Access Period
- Set to 4 ‘Any Time’
2 = Mode
- Set to ‘Direct Access’ if making calls into site from
Honeywell Remote Service Suite (RSS) for remote access
directly or via the IRIS Remote Service App client.
- Set to ‘MGR Authorise’ if making the remote access calls
out from site to the Honeywell RSS, and then set the ‘call
IP1’ IP address to the IP address for the Honeywell RSS
communication server e.g. 80.176.196.135
Note: The IRIS Touch does not support the Honeywell Encryption as uses its own encryption so please
ensure the following 2 options are turned off.
9 = Encrypt
1 = Alarm Report
- Set to Off
2 = Remote Access
- Set to Off
After you have entered in the relevant information exit Engineer Mode and the panel should now detect 2 new
RS485 modules (Comms Mod 4 & Keypad 15).
If the new modules are not detected then you may need to power off the Galaxy panel, check the dialler
connections, and power back on.
Now go back into Engineer Mode and select the menu option sequence 56.04.05 ‘ENGINEER TEST’ and send the test
alarm. Check to see if this test alarm has been received by the monitoring centre (ARC).
Note: If you are required to default the IRIS Touch dialler and start again you can do this by setting the primary IP
address within the Galaxy menu 56.04.02.02 to an IP address of 127.0.0.1.
You can now perform the alarm signals commissioning and sign off required by the monitoring centre (ARC).