background image

1

2

Use Purpose

NR8-200,  NR8-630  electronic  overload  relay  (hereinafter  referred  to  as  relay)  is  applicable  to  circuits 

with frequency of AC 50Hz or 60Hz, rated operating voltage up to 690V and current from 80A to 630A. It is 
used  for  overload  protection  and  phase-failure  protection  of  3-phase  AC  motor.  It  can  also  be  used  with 
corresponding contactor to act as magnetic starter.

Main Technical Parameters

01

NR8-200

NR8-630 Electronic Overload Relay

Table 1 Environmental conditions

Ambient temp. (℃)

Hot and humid atmospheric conditions

Altitude

Pollution class/installation category

-

5℃~+40℃, average temperature should not 35℃ within 24h

Relative humidity should not exceed 50% at +40℃; up to 90% at +20℃;

No influence below 2000m

Class 3/III

2.1

 See Table 1 and Table 2 for product technical parameters.

Environmental conditions

Table 2 Technical parameters

Model

Phase-failure protection

Reset function

Release indication

Test function

Emergency stop function

Setting current range (A)

Matching contactor

Auxiliary contacts

Rated insulation voltage Ui

Rated operating voltage Ue

Rated impulse withstand voltage Uimp

Yes

Manual reset

Yes

Yes

Yes

NR8-200

NR8-630

Yes

Manual reset

Yes

Yes

Yes

1NO+1NC

690V

660V/690V and below

6kV

5A

220V/230V 2.5A; 380V/400V 1.5A

220V 0.2A

IP00

80-160

100-200

125-250

200-400

315-630

NC8-115 175

NC8-205 500

Protection class

Ith

AC-15

DC-13

Auxiliary circuit

Summary of Contents for NR8-200

Page 1: ...NO 2020 05 Standard IEC EN 60947 4 1 User Instruction NR8 200 NR8 630 Electronic Overload Relay ...

Page 2: ...n and maintenance Installation in any damp condensed phase environment with inflammable and explosive gas is forbidden When the product is being installed or maintained the power must be switched off You are prohibited from touching the conductive part when the product is operating ...

Page 3: ...ge temperature should not exceed 35 within 24h Relative humidity should not exceed 50 at 40 up to 90 at 20 No influence below 2000m Class 3 III 2 1 See Table 1 and Table 2 for product technical parameters Environmental conditions Table 2 Technical parameters Model Phase failure protection Reset function Release indication Test function Emergency stop function Setting current range A Matching conta...

Page 4: ...relay operation time current characteristic curve 3 phase thermal state Figure 1 Relay time current characteristic curve 3 Installation 3 1 Installation Figure 2 Product overall dimensions NR8 200 95 96 97 98 NC NO 100 120 140 160 180 200 Stop Test Reset NR8 200 1 L1 3 L2 5 L3 2 T1 4 T2 6 T3 104 0 35 128 0 7 134 0 7 104 0 35 141 2 0 9 M8 Unit mm ...

Page 5: ... 96 97 98 NC NO Stop Test Reset NR8 630 1 L1 3 L2 5 L3 2 T1 4 T2 6 T3 128 0 4 156 0 7 155 0 7 104 0 35 161 0 9 M10 Table 3 Wiring torque reference M8 10N m M10 20N m M3 5 1 2N m NR8 200 NR8 630 NR8 200 NR8 630 2 mm 2 mm 2 mm 2 mm 2 mm 2 mm 25 95 50 2 185 0 75 2 5 0 75 2 5 0 75 2 5 0 75 2 5 0 75 2 5 0 75 2 5 A 3 5mm L 8mm S ...

Page 6: ...g red light off Green light flashing red light on Green light on red light flashing 4 Maintenance Clean the dust on the electronic overload relay timely Conduct product test and maintenance every half a year to ensure the smooth operation of the product and the good contact of NO and NC contacts Tighten the terminal screws with specified torque and align the load protection capability of the elect...

Page 7: ...t or product parts should be disposed of according to the industrial waste treatment process or be sent to the recycling station for assortment dismantling and recycling according to local regulations Check installation status and conduct troubleshooting Do not place the product in environment with strong shock or vibration Strong shock or vibration Change to product with smaller size The size is ...

Page 8: ...QC PASS Test date Please see the packing ZHEJIANG CHINT ELECTRICS CO LTD NR8 200 NR8 630 Electronic Overload Relay IEC EN 60947 4 1 Check 23 07 NR8 200 NR8 630 Electronic Overload Relay ...

Page 9: ...ectronic Overload Relay User Instruction Zhejiang Chint Electrics Co Ltd Add No 1 CHINT Road CHINT Industrial Zone North Baixiang Yueqing Zhejiang 325603 P R China E mail global sales chint com Website http en chint com ...

Reviews: