7. Communication command table
When the data (setting value) has a decimal point, remove the decimal point and represent it as a
whole number, then express it in hexadecimal figures.
Private
command
type
Modbus
function
code
Data item
Data
20H/50H 03H/06H 0001H: SV
Setting value
20H/50H 03H/06H 0002H: Not used
20H/50H 03H/06H 0003H: AT setting
0000H: Cancel 0001H: Perform
20H/50H 03H/06H 0004H: OUT proportional band setting
Setting value
20H/50H 03H/06H 0005H: Not used
20H/50H 03H/06H 0006H: Integral time setting
Setting value
20H/50H 03H/06H 0007H: Derivative time setting
Setting value
20H/50H 03H/06H 0008H: OUT pulse cycle setting
Setting value
20H/50H 03H/06H 0009H: Not used
20H/50H 03H/06H 000AH: Manual reset setting
Setting value
20H/50H 03H/06H 000BH: Alarm setting
Setting value
20H/50H 03H/06H 000CH: Not used
20H/50H 03H/06H 000DH: Not used
20H/50H 03H/06H 000EH: Not used
20H/50H 03H/06H 000FH: HB (Heater disconnection alarm)
setting
Setting value
20H/50H 03H/06H 0010H: LA (Loop break alarm) time
setting
Setting value
20H/50H 03H/06H 0011H: LA (Loop break alarm) span
setting
Setting value
20H/50H 03H/06H 0012H: Setting value lock selection
(*1)
0000H: Unlock 0002H: Lock 2
0001H: Lock 1 0003H: Lock 3
20H/50H 03H/06H 0013H: Not used
20H/50H 03H/06H 0014H: Not used
20H/50H 03H/06H 0015H: Sensor correction value setting
Setting value
20H/50H 03H/06H 0016H: Not used
20H/50H 03H/06H 0017H: Not used
20H/50H 03H/06H 0018H: Scaling high limit setting
Setting value
20H/50H 03H/06H 0019H: Scaling low limit setting
Setting value
20H/50H 03H/06H 001AH: Decimal point place selection
0
000H: XXXX (No decimal point)
0
001H: XXX.X (1 digit after decimal
point)
0
002H: XX.XX (2 digits after decimal
point)
0
003H: X.XXX (3 digits after decimal
point)
20H/50H 03H/06H 001BH: PV filter time constant setting
Setting value
20H/50H 03H/06H 001CH: OUT high limit setting
Setting value
20H/50H 03H/06H 001DH: OUT low limit setting
Setting value
20H/50H 03H/06H 001EH: OUT ON/OFF action
Hysteresis setting
Setting value
20H/50H 03H/06H 001FH: Not used
20H/50H 03H/06H 0022H: Not used
20H/50H 03H/06H 0023H: Alarm action selection (*2)
0000H: No alarm action
0001H: Deviation high alarm
0002H: Deviation low alarm
0003H: Absolute value deviation high alarm
0004H: Absolute value deviation low alarm
0005H: Absolute value high alarm
0006H: Absolute value low alarm
0007H: Deviation high alarm with standby
0008H: Deviation low alarm with standby
0009H: Absolute value deviation high
alarm with standby
20H/50H 03H/06H 0024H: Not used