20H/50H  03H/06H  0025H: Alarm deadband setting 

Setting value 

20H/50H  03H/06H  0026H: Not used 

 

20H/50H  03H/06H  0027H: Not used 

 

20H/50H  03H/06H  0028H: Not used 

 

20H/50H  03H/06H  0029H: Alarm action delayed timer 

setting 

Setting value 

20H/50H  03H/06H  002AH: Not used 

 

 

 

 

 

20H/50H  03H/06H  003FH: Not used 

 

20H/50H  03H/06H  0040H: Alarm action Energized/ 

Deenergized selection 

0000H: Energized   
0001H: Deenergized 

20H/50H  03H/06H  0041H: Not used 

 

20H/50H  03H/06H  0042H: Alarm HOLD function selection  0000H: HOLD function not applied 

0001H: HOLD function applied 

20H/50H  03H/06H  0043H: Not used 

 

20H/50H  03H/06H  0044H: Input type selection 

 

0000H: K          [–200 to 1370 ] 
0001H: K        [–199.9 to 400.0 ] 
0002H: J       

[–200 to 1000 ] 

0003H: R          

[0 to 1760 ] 

0004H: S          

[0 to 1760 ] 

0005H: B          

[0 to 1820 ] 

0006H: E           [–200 to 800 ] 
0007H: T        [–199.9 to 400.0 ] 
0008H: N          [–200 to 1300 ] 
0009H: PL-       

[0 to 1390 ] 

000AH: C (W/Re5-26)  [0 to 2315 ] 
000BH: Pt100      [–199.9 to 850.0 ] 
000CH: JPt100    [–199.9 to 500.0 ] 
000DH: Pt100       [–200 to 850 ] 
000EH: JPt100      [–200 to 500 ] 
000FH: K          [–320 to 2500 ] 
0010H: K        [–199.9 to 750.0 ] 
0011H: J     

[–320 to 1800 ] 

0012H: R          

[0 to 3200 ] 

0013H: S          

[0 to 3200 ] 

0014H: B          

[0 to 3300 ] 

0015H: E          [–320 to 1500 ] 
0016H: T        [–199.9 to 750.0 ] 
0017H: N          [–320 to 2300 ] 
0018H: PL-       

[0 to 2500 ] 

0019H: C (W/Re5-26)  [0 to 4200 ] 
001AH: Pt100      [–199.9 to 999.9 ] 
001BH: JPt100  [–199.9 to 900.0 ] 
001CH: Pt100          [–300 to 1500 ] 
001DH: JPt100      [–300 to 900 ] 
001EH: 4 to 20mA DC[–1999 to 9999] 
001FH: 0 to 20mA DC[–1999 to 9999] 
0020H: 0 to 1V DC  [–1999 to 9999] 
0021H: 0 to 5V DC    [–1999 to 9999] 
0022H: 1 to 5V DC    [–1999 to 9999] 
0023H: 0 to 10V DC  [–1999 to 9999] 

20H/50H  03H/06H  0045H: Direct/Reverse action selection  0000H: Heating (Reverse action) 

0001H: Cooling (Direct action) 

20H/50H  03H/06H  0046H: Not used 

 

20H/50H  03H/06H  0047H: AT bias setting 

Setting value 

20H/50H  03H/06H  0048H: ARW (anti-reset windup) 

setting 

Setting value 

20H/50H  03H/06H  006FH: Key Lock selection 

0000H: Key enabled     
0001H: Key Lock 

50H 

06H 

0070H: Key operation change flag 

clearing 

0000H: No action          
0001H: All clearing 

 
 

Summary of Contents for GT120 Series

Page 1: ...ck 1 System configuration RS 485 multi drop connection communication Option Fig 1 1 Fig 1 2 2 Wiring connection When using line converter SC8 10 Connector D sub 25 pin Connection RS 232C RS 485 Communication speed 2400 4800 9600 19200bps Fig 2 1 Host computer GT120 No 0 No 1 No 30 GT8 CDD GT8 CDM Shield wire SD 2 RD 3 SG 7 FG 1 RS 4 CS 5 DR 6 ER 20 CD 8 Host computer D sub connector 25 pin 4 3 RS ...

Page 2: ...For the instrument number setting and communication speed selection refer to the instruction manual for GT120 4 Communication procedure Communication starts with command transmission from the host computer hereafter Master and ends with the response of the GT120 hereafter Slave Response with data When the master sends the reading command the slave responds with the corresponding setting value or c...

Page 3: ...ata in command is transmitted as ASCII characters Data format Start bit 1 bit Data bit 7 bits Parity Even Stop bit 1 bit Error detection Checksum 5 2 Command configuration All commands are composed of ASCII The data setting value decimal number is represented with hexadecimal number and ASCII code is used The negative numbers are represented with 2 s complement 1 Setting command Fig 5 2 1 2 Readin...

Page 4: ...ter side as well to calculate the checksum of the response data from the slaves so that the communication errors can be checked The ASCII code hexadecimal which corresponds to the characters ranging from the address to that before the checksum is converted to binary notation and the total value is calculated The lower 2 digits of the total value are converted to 2 s complements and then to hexadec...

Page 5: ...en No Odd Selectable Stop bit 1 bit 2 bits Selectable Error detection LRC Longitudinal Redundancy Check Data interval 1 second or less 1 Message configuration ASCII mode message is configured to start by colon 3AH and end by CR carriage return 0DH LF Line feed 0AH See Fig 6 2 1 Fig 6 2 1 2 Slave address Slave address is an individual instrument number on the slave side and is set within the range ...

Page 6: ...ead and it is fixed as 30H 30H 30H 31H A response message from the slave in normal status When SV 100 Fig 6 2 3 The number of response bytes means the number of bytes of the data which has been read and it is fixed as 30H 32H A response message from the slave in abnormal status When non existent data item is sent Fig 6 2 4 The function code MSB is set to 1 for the response message in abnormal stat...

Page 7: ... 06H Setting to slaves Function code is used to discern whether the response is normal acknowledgement or if any error negative acknowledgement is occurred when the slave returns the response message to the master When acknowledgement is returned the slave simply returns the original function code When negative acknowledgement is returned the MSB of the original function code is set as 1 for the r...

Page 8: ... as 02H Response message from the slave in abnormal status When data item is mistaken Fig 6 3 4 The function code MSB is set to 1 for the response message in abnormal status 83H The abnormal code 02H Non existent data address is returned as contents of error 2 Setting Instrument number 1 SV 100 Request message from the master Fig 6 3 5 Response message from the slave in normal status Fig 6 3 6 Res...

Page 9: ...ction 1 0000H Unlock 0002H Lock 2 0001H Lock 1 0003H Lock 3 20H 50H 03H 06H 0013H Not used 20H 50H 03H 06H 0014H Not used 20H 50H 03H 06H 0015H Sensor correction value setting Setting value 20H 50H 03H 06H 0016H Not used 20H 50H 03H 06H 0017H Not used 20H 50H 03H 06H 0018H Scaling high limit setting Setting value 20H 50H 03H 06H 0019H Scaling low limit setting Setting value 20H 50H 03H 06H 001AH D...

Page 10: ...000BH Pt100 199 9 to 850 0 000CH JPt100 199 9 to 500 0 000DH Pt100 200 to 850 000EH JPt100 200 to 500 000FH K 320 to 2500 0010H K 199 9 to 750 0 0011H J 320 to 1800 0012H R 0 to 3200 0013H S 0 to 3200 0014H B 0 to 3300 0015H E 320 to 1500 0016H T 199 9 to 750 0 0017H N 320 to 2300 0018H PL 0 to 2500 0019H C W Re5 26 0 to 4200 001AH Pt100 199 9 to 999 9 001BH JPt100 199 9 to 900 0 001CH Pt100 300 t...

Page 11: ...git Converter function 0 Controller 1 Converter 214 digit Not used Always 0 215 digit Key operation change 0 No 1 Yes 20H 03H 0086H Not used 20H 03H 0087H Not used 20H 03H 00A0H Not used 20H 03H 00A1H Instrument information reading 0000 0000 0000 0000 215 to 20 20 digit Not used Always 0 21 digit Not used Always 0 22 digit Alarm function 0 Not applied 1 Applied 23 digit Not used Always 0 24 digit ...

Page 12: ...y check Checksum LRC CRC Data format Start bit 1 Data bit 7 8 Parity Even Odd No parity Stop bit 1 9 Troubleshooting If any malfunctions occur refer to the following items after checking the power supply to the master and the slave Problem If it is unable to communicate Check the following The connection or wiring of communication is not secure Burnout or imperfect contact on the communication cab...

Reviews: