11
20H
03H
0080H: PV (input value) reading
Present PV
20H
03H
0081H: MV (manipulated variable)
reading
Present MV
20H
03H
0082H: Not used
20H
03H
0083H: Not used
20H
03H
0084H: Not used
20H
03H
0085H: OUT status reading
0000 0000 0000 0000
2
15
to 2
0
2
0
digit: OUT
0: OFF 1: ON
2
1
digit: Not used (Always 0)
2
2
digit: Alarm output
0: OFF 1: ON
2
3
digit: Not used (Always 0)
2
4
digit: Not used (Always 0)
2
5
digit: Not used (Always 0)
2
6
digit: HB (Heater disconnection alarm)
output
0: OFF 1: ON
(When sensor burnout,
0: OFF)
2
7
digit: LA (Loop break alarm)
output
0: OFF 1: ON
2
8
digit: Overscale
0: OFF 1: ON
2
9
digit: Underscale
0: OFF 1: ON
2
10
digit: Not used (Always 0)
2
11
digit: AT
0: OFF 1: ON
2
12
digit: Not used (Always 0)
2
13
digit: Converter function
0: Controller 1: Converter
2
14
digit: Not used (Always 0)
2
15
digit: Key operation change
0: No 1: Yes
20H
03H
0086H: Not used
20H
03H
0087H: Not used
20H
03H
00A0H: Not used
20H
03H
00A1H: Instrument information reading 0000 0000 0000 0000
2
15
to 2
0
2
0
digit: Not used (Always 0)
2
1
digit: Not used (Always 0)
2
2
digit: Alarm function
0: Not applied
1: Applied
2
3
digit: Not used (Always 0)
2
4
digit: Not used (Always 0)
2
5
digit: Not used (Always 0)
2
6
digit: HB (Heater disconnection alarm)
0: Not applied
1: Applied
2
7
digit: LA (Loop break alarm)
0: Not applied
1: Applied
2
8
to 2
15
digit: Not used (Always 0)
(*1) When Lock 3 is designated, the set data is not saved in the memory.
This is why the setting value reverts to the one before Lock 3 when power is turned OFF.
(*2) When alarm action type is changed, the alarm setting value reverts to the default value and
alarm output status is also initialized.