- 81 -
[List of Recording data-Saving setting parameters]
Parameter
Function
Default
Set value
Format
Select format for recording to SD
card
Text
Binary:
Uses
“A4F” extension. Analysis software is
required for data replay.
Text:
Uses
“TXT” extension. Data can be replayed
with Microsoft Excel as needed.
Binary (float): Binary (floating decimal point)
Text (float):
Text (floating decimal point)
Start TRG.
Select trigger for recording start
Key
None (None), Key (started by REC + FUNC1 key), StartTime
(specified time), Alarm (linked to alarm output), EX (linked to
remote contact), Chart (linked to chart recording), Chart End
(linked to chart end), Timer (linked to calendar timer)
[StartTime]
Set recording start time when
selecting
“StartTime” for Start
TRG
*
00 : 00 to 23 : 59
End TRG.
Select trigger for recording stop
Key
Key (stopped by REC + FUNC1 key), Rec.time (specified
time), Alarm (linked to alarm output), EX (linked to remote
contact), Chart (linked to chart recording), Chart End (linked to
chart end), Timer (linked to calendar timer)
[Rec.time]
Set recording time when
selecting
“Rec.time” for End TRG
*
00 : 00 to 99: 59
Interval
Select interval of recording to SD
card
1sec
1sec, 2sec, 3sec, 5sec, 10sec, 15sec, 20sec, 30sec, 1min,
2min, 3min, 5min, 10min, 15min, 20min, 30min, 60min
PreTrigger
Past data for the specified
number of samples is recorded to
SD card when recording is
started
00
0 to 10
Note: Past data is initialized when settings are changed or
card is inserted/removed.
When PreTrigger is set, the recording interval
synchronizes with past data, so there may be a case
that measured data at recording start time is not
recorded.
Relay No.
Set alarm output No. used when
“Alarm” is selected for Start TRG
or End TRG
*
- (No output), 99 (internal circuit output), 1 to 6
EX No.
Set remote contact No. used
when
“EX” is selected for Start
TRG or End TRG
*
0 to 5
Timer No.
Set remote contact No. used
when
“Timer” is selected for Start
TRG or End TRG
*
0 to 5
[Restrictions on start/end trigger selection]
End trigger
Key
Specified
time
Alarm output
linked
Remote
contact
linked
Chart
recording
linked
Chart end
linked
Calendar
timer linked
S
ta
rt
t
rigg
e
r
None
x
x
x
x
x
x
x
Key
O
O
x
x
x
x
x
Specified time
O
O
x
x
x
x
x
Alarm output linked
O
O
O
x
x
x
x
Remote contact linked
O
O
x
O
x
x
x
Chart recording linked
x
O
x
x
O
x
x
Chart end linked
O
O
x
x
x
O
x
Calendar timer linked
O
O
x
x
x
x
O
Measured data file is divided by a certain number of bytes.
(The number of bytes varies by the number of recording channels, etc.)
File division
Note 5
A measured data file is saved in a folder created each month/year within the
“HR_DATA” folder (for example, a folder
is named
“HR201101” for Jan. 2011).
Also, a setting parameter file is saved in the
“HR_SET” folder.
File save location