Wiring
Power Wiring
Power to operate the Heating element in the In-line Heater(s) comes from a 2
pole 208 to 240 VAC GFCI circuit breaker, via an included 40a Solid State Relay
(SSR) used to provide real time control over the power level and manage the
rate of addition of heat to the Chiltrix main loop.
The power from one circuit breaker pole (L1) passes through the relay box and
connects directly to the in-line heater’s thermal overload interrupt device.
Power from the other circuit breaker pole(L2) is connected to the SSR and its
conductor is connected to the SSR’s terminal #2. The SSR’s terminal #1 is
connected to the in-line heater’s heating element. See below.
MAKE SURE GROUNDING IS DONE PROPERLY!