SKU 97580
For technical questions, please call 1-800-444-3353.
Page 8
the suffix “W-A” (“W” in Canada) to
indicate it is OK for outdoor use.
Make sure the extension cord is
6.
properly wired and in good electrical
condition. Always replace a damaged
extension cord or have it repaired by
a qualified electrician before using it.
Protect the extension cords from
7.
sharp objects, excessive heat, and
damp or wet areas.
Recommended minimum wiRe
gAuge FoR eXtension coRds*
(120/240 Volt)
nAmeplAte
AmpeRes
(at full load)
eXtension coRd
lengtH
25’
50’
75’
100’
150’
0 – 2.0
18
18
18
18
16
2.1 – 3.4
18
18
18
16
14
3.5 – 5.0
18
18
16
14
12
5.1 – 7.0
18
16
14
12
12
7.1 – 12.0
18
14
12
10
-
12.1 – 16.0
14
12
10
-
-
16.1 – 20.0
12
10
-
-
-
tABle A
* Based on limiting the line
voltage drop to five volts at
150% of the rated amperes.
symbology
Double Insulated
Canadian Standards Association
Underwriters Laboratories, Inc.
V~
Volts Alternating Current
A
Amperes
n0 xxxx/min.
No Load Revolutions per Minute
(RPM)